Alpha Alpha CD90S and 115S system (CD90S, CD115S)
System boiler (commercial, over 70 kW), natural gas and LPG
Combustion figures
| Figure | Natural gas (G20) | LPG (G31) |
|---|---|---|
CO₂ at high rate More infoHide infoMI section 2.8 Performance data, CH Max column. The table gives the tolerance as ± 0.2% for all figures. |
| 10.7% ± 0.2 |
CO₂ at low rate More infoHide infoMI section 2.8 Performance data, Min column. |
|
|
Maximum CO | Not given in MI | Not given in MI |
CO/CO₂ ratio More infoHide infoFrom the routine servicing notes (section 6): if the ratio measured before servicing is greater than 0.003 the heat exchanger needs cleaning, and after reassembly the ratio must be less than 0.003. Measured at the flue sampling point. | Less than 0.003 | Less than 0.003 |
O₂ | Not given in MI | Not given in MI |
Working inlet pressure More infoHide infoMeasurement point not stated in MI. Section 3.1 says to ensure the inlet supply pressure is at least 20 mbar for natural gas or 37 mbar for propane. The gas valve has an inlet gas pressure test point (Fig. 21). | At least 20 mbar | At least 37 mbar |
Gas rate at maximum More infoHide infoSection 2.1. Section 3.1 also gives the LPG gas rate as 7.17 kg/h (14 litres/h of liquid gas) for the CD90S and 8.76 kg/h (17.2 litres/h) for the CD115S. |
|
|
From 03/10/D243 (© Alpha Therm Limited 2010)
Enter service mode for high and low rate
High rate
Steps not added yet. Follow the MI.
Low rate
Steps not added yet. Follow the MI.
Ending the test: follow the MI.
Models
| Model | Gas |
|---|---|
| CD90S NG | NG |
| CD115S NG | NG |
| CD90S LPG | LPG |
| CD115S LPG | LPG |
Source: Alpha CD90S and 115S Installation and Servicing Instructions, 03/10/D243 (© Alpha Therm Limited 2010).
Sections: 2.1 Performance; 2.8 Performance data; 3.1 Gas supply; 5.2 Test for gas tightness and purge the supply; 6 Routine servicing.
Spotted something wrong? Tell us.
Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.