Alpha E-Tec combi (E-Tec 28, 33)

Combi, natural gas and LPG

Combustion figures

FigureNatural gas (G20)LPG (G31)
CO₂ at high rate
More infoHide infoMI figures for CO₂ at maximum DHW output, which is the 99% (Max DHW output) level in chimney sweep mode. The MI also gives CO₂ at maximum CH output with no tolerance (NG: E-Tec 28 9.7%, E-Tec 33 9.5%; LPG: E-Tec 28 11.4%, E-Tec 33 11.2%), but says CO₂ testing at the Max CH output level is not required. Check with the case fitted and wait about 30 seconds for the boiler to stabilise.
E-Tec 28
9.7% (+0.5/−0.2%)
E-Tec 33
9.5% (±0.2%)
E-Tec 28
11.4% (+0.1/−0.3)
E-Tec 33
11.2% (+0.2/−0.4)
CO₂ at low rate
More infoHide infoCO₂ at minimum output, the 0% (low fire) level in chimney sweep mode. Check with the case fitted.
E-Tec 28
8.8% (+0.2/−0.3%)
E-Tec 33
8.6% (+0.2/−0.3%)
E-Tec 28
10.6% (+0.3/−0.1)
E-Tec 33
10.0% (+0.4/−0.2)
Maximum CO
More infoHide infoThe LPG table does not list CO; the MI says other technical data for LPG is the same as NG data.
450 ppm450 ppm
CO/CO₂ ratio
More infoHide infoThe LPG table does not list the ratio; the MI says other technical data for LPG is the same as NG data. The servicing section asks for further checks if the ratio is greater than 0.004.
0.0040.004
O₂
Not given in MINot given in MI
Working inlet pressure
More infoHide infoGiven as the gas supply pressure in the technical data tables. Measurement point not stated in MI.
20 mbar37 mbar
Gas rate at maximum
More infoHide infoGas rate at maximum output.
E-Tec 28
3.05 m³/h
E-Tec 33
3.45 m³/h
E-Tec 28
2.24 kg/h (0.62 g/s)
E-Tec 33
2.53 kg/h (0.7 g/s)

From Part No. 1.042188 rev. ST.003781.001, 1018/D385

Enter service mode for high and low rate

High rate

  1. With no heating or hot water demand, hold RESET for 8 seconds. The parasol and snowman symbols flash together.
  2. If a Climatic controller is fitted it shows ERR>07. That’s not a fault.
  3. Press DHW up ▲ (tap symbol) until it’s at 99%, maximum. The levels are 0%, 80–90% and 99%.

Low rate

  1. Press DHW down ▼ (tap symbol) to set 0%, minimum.
  2. Press DHW up ▲ to go back to maximum.
Ending the test
  • Hold Off/Stand-by/Summer/Winter for 8 seconds to turn the boiler off and come out. It also ends by itself after 15 minutes.

Models and GC numbers

ModelGC numberGas
E-Tec 28 (NG)47-532-69NG
E-Tec 33 (NG)47-532-70NG
E-Tec 28 (LPG)47-532-73LPG
E-Tec 33 (LPG)37-532-74LPG

Source: Alpha E-Tec 28 and 33 Installation and Servicing Instructions, Part No. 1.042188 rev. ST.003781.001, 1018/D385.

Sections: 3.1 Technical performance data - natural gas; 3.2 Technical performance data - LPG; 6.6 Checking the combustion - chimney sweep mode; 6.11 Converting the boiler to operate on LPG; 6.12 CO2 set up procedure; 7 Routine servicing (combustion check).

Spotted something wrong? Tell us.

Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.