Alpha E-Tec Plus combi (28, 33, 38)
Combi, natural gas (LPG by conversion kit)
Combustion figures
| Figure | Natural gas (G20) | LPG (G31) |
|---|---|---|
CO₂ at high rate More infoHide infoCO₂ at maximum DHW output (99% in chimney sweep mode), which is the maximum the MI checks and sets (MI 6.6, 6.12). Check with the case fitted; after any gas valve adjustment wait about 30 seconds for the boiler to stabilise. The MI also gives CO₂ at maximum CH output with no tolerance: NG 28: 9.7%, 33: 9.5%, 38: 9.2%; LPG 28: 11.4%, 33: 11.2%, 38: 10.85%. MI 6.6 says CO₂ testing at maximum CH output (80–90%) is not required. MI 6.6 refers to Section 2.1 for the tolerance, but 2.1 is Electrical supply; MI 6.12 points to Section 3.1. |
|
|
CO₂ at low rate More infoHide infoAt minimum output (0% in chimney sweep mode), case fitted (MI 6.12). |
|
|
Maximum CO More infoHide infoThe LPG table (MI 3.2) gives no CO figure and says other technical data is the same as NG data. | 450 ppm | 450 ppm |
CO/CO₂ ratio More infoHide infoGiven as Maximum CO/CO₂ ratio in MI 3.1. MI 7 says the ratio should be less than 0.004. The LPG table says other technical data is the same as NG data. | 0.004 | 0.004 |
O₂ | Not given in MI | Not given in MI |
Working inlet pressure More infoHide infoMeasurement point not stated in MI. Given as Gas supply pressure in the technical data (MI 3.1, 3.2), with no range. | 20 mbar | 37 mbar |
Gas rate at maximum |
|
|
From Part No. 1.043044 rev. ST.004614/001 (0220/D409)
Enter service mode for high and low rate
High rate
- With no heating or hot water demand, hold RESET for 8 seconds. The parasol and snowman symbols flash together.
- Press the hot water ▲ button (tap symbol) to step up to maximum, 99%. The levels are 0%, 80–90% and 99%.
- If a Climatic controller is fitted it shows ERR>07. That’s not a fault.
Low rate
- Press the hot water ▼ button (tap symbol) to step down to minimum, 0%.
Ending the test
- Turn the boiler off to come out (hold the Off/Stand-by/Summer/Winter button for 8 seconds). It also ends by itself after 15 minutes.
Models and GC numbers
| Model | GC number | Gas |
|---|---|---|
| Alpha E-Tec Plus 28 | 47-532-77 | NG |
| Alpha E-Tec Plus 33 | 47-532-78 | NG |
| Alpha E-Tec Plus 38 | 47-532-79 | NG |
Source: Alpha E-Tec Plus 28, 33 and 38 Installation and Servicing Instructions, Part No. 1.043044 rev. ST.004614/001 (0220/D409).
Sections: 3.1 Technical performance data - natural gas; 3.2 Technical performance data - LPG; 6.6 Checking the combustion - chimney sweep mode; 6.11 Converting the boiler to operate on LPG; 6.12 CO2 set up procedure; 7 Routine servicing (combustion check).
Spotted something wrong? Tell us.
Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.