Alpha E-Tec S system (E-Tec 20S, 30S)
System boiler, natural gas (LPG by conversion kit)
Combustion figures
| Figure | Natural gas (G20) | LPG (G31) |
|---|---|---|
CO₂ at high rate More infoHide infoCO₂ at maximum DHW output: 99% in chimney sweep mode, case fitted, at the flue test point. Section 2.1 also lists CO₂ at maximum CH output with no tolerance (NG 20S 9.7%, 30S 9.5%; LPG 20S 11.4, 30S 11.2); MI 5.6 says CO₂ testing at the 80–90% max CH output is not required. |
|
|
CO₂ at low rate More infoHide infoCO₂ at minimum output: 0% (low fire) in chimney sweep mode, case fitted, at the flue test point. |
|
|
Maximum CO More infoHide infoGiven in the NG table only. The LPG table says other technical data is the same as NG data. | 450 ppm | 450 ppm |
CO/CO₂ ratio More infoHide infoMaximum. MI section 6 says the ratio should be less than 0.004. Given in the NG table only; the LPG table says other technical data is the same as NG data. | 0.004 | 0.004 |
O₂ | Not given in MI | Not given in MI |
Working inlet pressure More infoHide infoMeasurement point not stated in MI. Given as Gas supply pressure in Section 2.1, with no tolerance. | 20 mbar | 37 mbar |
Gas rate at maximum More infoHide infoGas rate at maximum output, Section 2.1. |
|
|
From Part No. 1.041383 rev. ST.003581/001 (0518/D382)
Enter service mode for high and low rate
High rate
- With no heating or hot water demand, hold RESET for 8 seconds. The parasol and snowman symbols flash together.
- Press the hot water ▲ button (tap symbol, left-hand top) to step up to maximum, 99%. The levels are 0%, 80–90% and 99%.
- If a Climatic controller is fitted it shows ERR>07. That’s not a fault.
Low rate
- Press the hot water ▼ button (left-hand bottom) for minimum, 0%.
- Press the hot water ▲ button to go back to maximum.
Ending the test
- Turn the boiler off to come out: hold the Off/Stand-by/Summer/Winter button for 8 seconds. It also ends by itself after 15 minutes.
Models
| Model | Gas |
|---|---|
| E-Tec 20S | NG |
| E-Tec 30S | NG |
Source: Alpha E-Tec 20S and 30S installation and servicing instructions, Part No. 1.041383 rev. ST.003581/001 (0518/D382).
Sections: 2.1 Technical performance data; 2.6 Data badge annotation; 5.6 Checking the combustion - chimney sweep mode; 5.11 Converting the boiler to operate on LPG; 5.12 CO2 set up procedure; 6 Routine servicing (combustion check).
Spotted something wrong? Tell us.