Alpha InTec² XE combi (25XE, 28XE)
Combi, natural gas (LPG by conversion)
Combustion figures
| Figure | Natural gas (G20) | LPG (G31) |
|---|---|---|
CO₂ at high rate More infoHide infoMI gives this as CO₂ at maximum CH output, the figure checked in chimney sweep mode with the CH knob at maximum, front case fitted. MI also gives CO₂ at maximum DHW output (the 99% setting used in the CO₂ set up procedure): NG 25XE 9.2%, 28XE 9.1% (± 0.8); LPG 10.2% both sizes (± 1). CO₂ at medium output (ignition), checked with the display at 72 (25XE) or 56 (28XE): NG 9.0% both sizes (± 0.8); LPG 10.7% both sizes (± 1). NG tolerance printed as Factory set CO₂ (± 0.8%); LPG as % (±1%). |
|
|
CO₂ at low rate More infoHide infoMI gives this as CO₂ at minimum output, checked with the CH knob at minimum after the self-diagnosis symbol stops flashing. LPG table prints 10.0 for 25XE and 10 for 28XE. | 9.0% ± 0.8 | 10.0% ± 1 |
Maximum CO More infoHide infoPrinted as CO (max) in the NG table. The LPG table says other technical data is the same as NG data. | 200 ppm | 200 ppm |
CO/CO₂ ratio More infoHide infoPrinted as Maximum CO/CO₂ in the NG table; the LPG table says other technical data is the same as NG data. Section 6 says to investigate if the measured ratio is greater than 0.003. | 0.003 | 0.003 |
O₂ | Not given in MI | Not given in MI |
Working inlet pressure More infoHide infoPrinted as Gas supply pressure in the technical data, with no range. Measurement point not stated in MI. Section 6 says to check the working gas inlet pressure at maximum rate; the gas valve has an inlet pressure test point (Fig. 5.2). | 20 mbar | 37 mbar |
Gas rate at maximum More infoHide infoNG printed as Gas rate at max. output. The LPG table prints it just as Gas rate. |
|
|
From Part No. 1.038088 rev. ST.001590/000 0315/D343
Enter service mode for high and low rate
High rate
- Keep the front case fitted. With no heating or hot water demand, hold RESET for 8 seconds.
- The parasol and snowman symbols flash together. A Climatic controller, if fitted, shows ERR>07. That’s not a fault.
- Turn the central heating knob to maximum. Display shows 99.
Low rate
- Turn the central heating knob to minimum. Display shows 00.
- For the medium (ignition) check, turn the knob until the display shows 72 (25XE) or 56 (28XE).
Ending the test
- Turn the boiler off to come out. It also ends by itself after 15 minutes.
Models
| Model | Gas |
|---|---|
| InTec² 25XE | NG |
| InTec² 28XE | NG |
Source: Alpha InTec² 25XE and 28XE Installation and Servicing Instructions, Part No. 1.038088 rev. ST.001590/000 0315/D343.
Sections: 2.1 Technical performance data; 2.6 Data badge annotation; 5.3 Test for gas tightness and purge the supply; 5.7 Checking the combustion - chimney sweep mode; 5.12 Converting the boiler to operate on LPG; 5.13 CO2 set up procedure; 5.14 Programming the PCB; 6 Routine servicing (combustion check).