Baxi Checked against MI

Baxi 400 Heat (412, 415, 418, 424, 430)

Heat only, natural gas

Combustion figures

FigureNatural gas (G20)
CO₂ at high rate
More infoHide infoFrom Setting the Gas Valve (MI 10.3.11), probe in the flue sampling point. The MI does not say whether the case should be on or off for this check. There must always be a difference of 0.4% between the maximum and minimum CO₂ readings.
9.3% ±0.1%
CO₂ at low rate
More infoHide infoRe-check both maximum and minimum if any adjustment has been made.
8.9% ±0.1%
Maximum CO
More infoHide infoApplies at both maximum and minimum rate (commissioning flow chart, MI 7.4.2).
< 350 ppm
CO/CO₂ ratio
More infoHide infoAt both maximum and minimum rate (MI 7.4.2, 10.1 and 10.3.11). The Technical Data table (MI 3.1) words it as up to a maximum of 0.004.
< 0.004
O₂
More infoHide infoThe MI gives O₂ only for the flue integrity check at the air inlet.
Not given in MI
Working inlet pressure
More infoHide infoAt the gas meter: 19–23 mbar. Checked at maximum rate; the text says at least 17 mbar at the valve and 18 mbar at the gas cock. Nominal dynamic inlet pressure 20 mbar (MI 3.1). Permissible pressure drop across system pipework ≤ 1 mbar.
Appliance inlet
18–22 mbar
Gas valve test point
17–21 mbar
Gas rate at maximum
More infoHide infoNatural gas G20, after 10 minutes, with any other appliances and pilot lights off.
412
1.42 m³/hr
415
1.75 m³/hr
418
2.07 m³/hr
424
2.73 m³/hr
430
3.27 m³/hr
Flue integrity
More infoHide infoAt the air inlet (air sampling) test point, boiler at maximum rate.
O₂ ≥ 20.6%
CO₂ < 0.2%

From 7684223-01 (06/17)

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
Baxi 412 Heat ErP41-470-50NG
Baxi 415 Heat ErP41-470-51NG
Baxi 418 Heat ErP41-470-52NG
Baxi 424 Heat ErP41-470-53NG
Baxi 430 Heat ErP41-470-54NG

Source: Baxi 400 Heat Installation and Service Manual, 7684223-01 (06/17).

Sections: 3.1 Technical Data; 7.4.1 Chimney Sweep Mode; 7.4.2 Chimney Sweep Mode - Combustion Check; 7.5.1 Check the Operational (Working) Gas Inlet Pressure; 10.1 General; 10.3.11 Setting the Gas Valve (CO2 Check).

Spotted something wrong? Tell us.

Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.