Baxi Baxi Combi (624, 630)

Combi, natural gas

Combustion figures

FigureNatural gas (G20)
CO₂ at high rate
More infoHide infoPrinted as 9.0 + 0.3 – 0.2 (% maximum), the same for both sizes, in Tab.23 (9.3.12) and in Setting the gas valve (CO₂). Case front panel fitted. Checked in calibration (chimney sweep) mode after running the boiler for several minutes.
9.0% +0.3 / −0.2
CO₂ at low rate
More infoHide infoPrinted as 8.5 + 0.1 – 0.4 (% minimum), the same for both sizes, in Tab.23 (9.3.12) and in Setting the gas valve (CO₂).
8.5% +0.1 / −0.4
Maximum CO
More infoHide infoAt maximum and minimum rate, from the combustion procedure flow chart (Fig.47).
<350 ppm
CO/CO₂ ratio
More infoHide infoAt maximum and minimum rate (Fig.47, 9.1 and Setting the gas valve).
<0.004
O₂
More infoHide infoThe MI gives O₂ only for the flue integrity check at the air inlet test point.
Not given in MI
Working inlet pressure
More infoHide infoFrom Fig.43 (gas meter to valve). At the meter: 19–23 mbar. The text says the working pressure at the inlet gas pressure test point (A, on the gas cock) must be at least 18 mbar with the boiler at maximum rate. Nominal dynamic inlet pressure 20 mbar (G20).
Appliance inlet
18–22 mbar
Gas valve test point
17–21 mbar
Gas rate at maximum
More infoHide infoNatural gas (G20), with all other appliances and pilot lights off. Minimum rate (Qmin) 0.67 m³/h for both sizes (Tab.8).
624
2.71 m³/h
630
3.26 m³/h
Flue integrity
More infoHide infoAt the air inlet test point on the flue adaptor, boiler at maximum rate.
O₂ ≥ 20.6%
CO₂ < 0.2%

From 7679306 - 1 - 10082017

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
Baxi Combi 62447-077-28NG
Baxi Combi 63047-077-29NG

Source: Baxi Combi 624 &mdash; 630 Installation and Service Manual, 7679306 - 1 - 10082017.

Sections: 3.1.3 Gas category; 3.2.1 Technical information (Tab.5, Tab.8); 7.4.1 Check the operational (working gas inlet pressure and gas rate); 7.4.2 Checking combustion - chimney sweep mode; 9.1 General; 9.3.12 Gas valve (Tab.23, Setting the gas valve (CO₂)).