Baxi Baxi 600 Heat (613, 616, 619, 625, 630)
Heat only, natural gas
Combustion figures
| Figure | Natural gas (G20) |
|---|---|
CO₂ at high rate More infoHide infoFrom Setting the gas valve (MI 10.3.11), maximum rate in chimney sweep mode. The MI says there must always be a difference of 0.4% between the maximum and minimum CO₂ readings. Same figure for all sizes. | 9.3% ±0.1% |
CO₂ at low rate More infoHide infoFrom Setting the gas valve (MI 10.3.11), minimum rate in chimney sweep mode. Same figure for all sizes. | 8.9% ±0.1% |
Maximum CO More infoHide infoFrom the combustion check flow chart (MI 7.4.2), measured at the flue gas test point. |
|
CO/CO₂ ratio More infoHide infoFlow chart (MI 7.4.2) and MI 10.1 say less than 0.004. Technical data (MI 3.1) words it as up to a maximum of 0.004. |
|
O₂ | Not given in MI |
Working inlet pressure More infoHide infoAt maximum rate (MI 7.5.1, Fig. 41). The text says at least 17 mbar at the valve and 18 mbar at the gas cock. At the gas meter: 19–23 mbar. Nominal dynamic inlet pressure 20 mbar (MI 3.1). Permissible pressure drop across system pipework ≤ 1 mbar. |
|
Gas rate at maximum More infoHide infoNatural gas G20, after 10 minutes (MI 3.1). Measure with other appliances and pilot lights off (MI 7.5.1). |
|
Flue integrity More infoHide infoAt the air inlet test point, boiler at maximum rate (MI 7.4.2 and 10.1). | O₂ ≥ 20.6% CO₂ < 0.2% |
From 7726858-01 (1/19)
Enter service mode for high and low rate
High rate
Steps not added yet. Follow the MI.
Low rate
Steps not added yet. Follow the MI.
Ending the test: follow the MI.
Models and GC numbers
| Model | GC number | Gas |
|---|---|---|
| Baxi 613 Heat | 41-470-66 | NG |
| Baxi 616 Heat | 41-470-67 | NG |
| Baxi 619 Heat | 41-470-68 | NG |
| Baxi 625 Heat | 41-470-69 | NG |
| Baxi 630 Heat | 41-470-70 | NG |
Source: Baxi 600 Heat installation and service manual, gas fired wall mounted condensing boiler (Heat 613 - 616 - 619 - 625 - 630), 7726858-01 (1/19).
Sections: 3.1 Technical Data; 7.4.1 Chimney Sweep Mode (CSM); 7.4.2 Chimney Sweep Mode - Combustion Check; 7.5.1 Check the Operational (Working) Gas Inlet Pressure; 10.1 General; 10.3.11 Setting the Gas Valve (CO2 Check).
Spotted something wrong? Tell us.
Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.