Baxi Checked against MI

Baxi Baxi 800 Combi (825, 830, 836)

Combi, natural gas

Combustion figures

FigureNatural gas (G20)
CO₂ at high rate
More infoHide infoPrinted as 9.0 + 0.3 – 0.2 (% maximum), the same for all three sizes, in Tab.23 and in Setting the gas valve (MI 9.3.12). Case front panel fitted. Set in calibration mode, display 100.
9.0% + 0.3 – 0.2
CO₂ at low rate
More infoHide infoPrinted as 8.5 + 0.1 – 0.4 (% minimum), the same for all three sizes, in Tab.23 and in Setting the gas valve (MI 9.3.12). Display 0 at minimum rate.
8.5% + 0.1 – 0.4
Maximum CO
More infoHide infoChecked at both maximum and minimum rate (MI Fig.47 Combustion procedure).
< 350 ppm
CO/CO₂ ratio
More infoHide infoChecked at both maximum and minimum rate (MI Fig.47). MI 9.1 and 9.3.12 also say it must be less than 0.004.
< 0.004
O₂
More infoHide infoThe MI gives O₂ only for the flue integrity check at the air inlet test point (see Flue integrity).
Not given in MI
Working inlet pressure
More infoHide infoFrom MI Fig.43. At the meter: 19–23 mbar. MI 7.4.1: with the boiler at maximum rate, the working pressure at the gas inlet test point (A) must be at least 18 mbar. Fault finding (MI Fig.73) gives a minimum of 17 mbar at the gas valve.
Appliance inlet
18–22 mbar
Gas valve test point
17–21 mbar
Gas rate at maximum
More infoHide infoNatural gas (G20), with all other appliances and pilot lights off (MI 7.4.1 Tab.22; also Tab.8).
825
2.71 m³/h
830
3.26 m³/h
836
3.81 m³/h
Flue integrity
More infoHide infoAt the air inlet test point, boiler at maximum rate (MI Fig.47 and 9.1).
O₂ ≥ 20.6%
CO₂ < 0.2%

From 7728205-01

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
Baxi 800 Combi 82547-077-38NG
Baxi 800 Combi 83047-077-39NG
Baxi 800 Combi 83647-077-40NG

Source: Baxi Combi 825 - 830 - 836 Installation and Service Manual (High Efficiency Wall Hung Condensing Gas Boiler), 7728205-01.

Sections: 3.2 Technical data; 7.4.1 Check the operational (working) gas inlet pressure and gas rate; 7.4.2 Checking combustion - chimney sweep mode (Fig.46, Fig.47 Combustion procedure); 9.1 General; 9.3.12 Gas valve (Setting the gas valve); 10.2.4 Fault finding solutions sections F to H.

Spotted something wrong? Tell us.

Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.