Baxi Baxi 800 System (818, 824)

System boiler, natural gas

Combustion figures

FigureNatural gas (G20)
CO₂ at high rate
More infoHide infoCase front panel on (MI Tab.22). With the case front panel off: 8.8% +0.3 −0.2. The Setting the gas valve table (MI 9.3.8) gives 8.8% +0.3 −0.2 at maximum without saying case on or off, which matches the case-off figure. The MI says the case front panel must be fitted when checking combustion (MI 7.4.2).
9.0% +0.3 −0.2
CO₂ at low rate
More infoHide infoCase front panel on (MI Tab.22). With the case front panel off: 8.3% +0.1 −0.4. The Setting the gas valve table (MI 9.3.8) gives 8.3% +0.1 −0.4 at minimum without saying case on or off, which matches the case-off figure.
8.5% +0.1 −0.4
Maximum CO
More infoHide infoAt both maximum and minimum rate, measured at the flue gas test point (MI Fig.40 Combustion procedure).
<350 ppm
CO/CO₂ ratio
More infoHide infoAt both maximum and minimum rate (MI Fig.40). MI 9.1 and 9.3.8 also say it must be less than 0.004.
<0.004
O₂
Not given in MI
Working inlet pressure
More infoHide infoWith the boiler at maximum rate. At the meter: 19–23 mbar (MI Fig.36). The MI also says the inlet test point (A) must be at least 18 mbar, the permissible pressure drop across system pipework is 1 mbar or less, the minimum at the meter is 19 mbar (MI 10.1.1) and the minimum at the gas valve is 17 mbar (MI 10.2.3). Dynamic (nominal) inlet pressure 20 mbar.
Appliance inlet
18–22 mbar
Gas valve test point
17–21 mbar
Gas rate at maximum
More infoHide infoNatural gas (G20) Qmax, with all other appliances and pilot lights off. Qmin is 0.49 m³/h on both sizes (MI Tab.21).
18
1.96 m³/h
24
2.61 m³/h
Flue integrity
More infoHide infoAt the incoming air test point on the flue adaptor, boiler at maximum rate (MI Fig.40 and 9.1).
O₂ ≥ 20.6%
CO₂ < 0.2%

From 7729931-01

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
818 System (18)41-470-73NG
824 System (24)41-470-74NG

Source: Baxi System 818 - 824 Installation and Service Manual (High Efficiency Wall Hung Condensing Gas Boiler), 7729931-01.

Sections: 3.1.3 Gas category; 3.2.1 Technical information (Tab.5, Tab.7); 7.4.1 Check the operational (working gas inlet pressure and gas rate); 7.4.2 Checking combustion - chimney sweep mode (Fig.39, Fig.40 Combustion procedure); 9.1 General (Check the Combustion Performance); 9.3.8 Gas valve (Tab.22, Setting the gas valve); 10.1.1 Initial error fault finding checks; 10.2.3 Fault finding solutions sections F to H.