Baxi Checked against MI

Baxi Assure Combi (25, 30, 36, 25 LPG, 30 LPG, 36 LPG)

Combi, natural gas and LPG

Combustion figures

FigureNatural gas (G20)LPG (G31)
CO₂ at high rate
More infoHide infoPrinted as a plus and minus tolerance, e.g. 9.0 + 0.3 – 0.2 means 0.3 above and 0.2 below. From the gas valve setting table (MI 9.3.12 Tab.23 and Setting the gas valve), checked in calibration mode. MI 7.4.2 says the case front panel must be fitted when checking combustion. The commissioning check in MI 7.4.2 gives only CO and CO/CO₂ ratio limits.
9.0% + 0.3 – 0.210.5% + 0.5 – 0.1
CO₂ at low rate
More infoHide infoNG figure is printed 8.5 + 0.1 – 0.4 in Tab.23 and 8.5 + 0.1 — 0.4 (longer dash) in the Setting the gas valve steps; taken as the same figure.
8.5% + 0.1 – 0.410.0% + 0.1 – 0.5
Maximum CO
More infoHide infoFrom the combustion procedure flowchart (MI 7.4.2 Fig.46), with the case front panel fitted. The MI says NG and LPG data are the same unless stated otherwise.
Max rate
< 350ppm
Min rate
< 350ppm
Max rate
< 350ppm
Min rate
< 350ppm
CO/CO₂ ratio
Max rate
< 0.004
Min rate
< 0.004
Max rate
< 0.004
Min rate
< 0.004
O₂
Not given in MINot given in MI
Working inlet pressure
More infoHide infoNG: at the meter 19–23 mbar (MI 7.4.1 Fig.42). Checked at maximum rate; the MI also says the inlet test point pressure must be at least 18 mbar. LPG: supply pressure from the gas category table (MI 14.3). Measurement point not stated in MI. The MI gives no LPG version of the NG pressure diagram.
Appliance inlet
18–22 mbar
Gas valve test point
17–21 mbar
37 mbar
Gas rate at maximum
More infoHide infoMeasured with any other appliances and pilot lights turned off (MI 7.4.1).
25
2.71 m³/h
30
3.26 m³/h
36
3.81 m³/h
25
1.98 kg/h
30
2.38 kg/h
36
2.83 kg/h
Flue integrity
More infoHide infoAt the air inlet test point, boiler at maximum rate.
O₂ ≥ 20.6%
CO₂ < 0.2%
O₂ ≥ 20.6%
CO₂ < 0.2%

From 7750729-01

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
Assure Combi 2547-077-42NG
Assure Combi 3047-077-43NG
Assure Combi 3647-077-44NG
Assure Combi 25 LPG47-077-45LPG
Assure Combi 30 LPG47-077-46LPG
Assure Combi 36 LPG47-077-47LPG

Source: Baxi Assure Combi 25 - 30 - 36, 25 LPG - 30 LPG - 36 LPG installation and service manual, 7750729-01.

Sections: 3.1.3 Gas category; 3.2.1 Technical information; 7.4.1 Check the operational (working gas inlet pressure and gas rate); 7.4.2 Checking combustion - chimney sweep mode; 9.1 General; 9.3.12 Gas valve; 14.3 Differences for LPG models.

Spotted something wrong? Tell us.

Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.