Baxi Bermuda BBU 15 HE condensing back boiler (BBU 15 HE)

Condensing back boiler unit, natural gas

Combustion figures

FigureNatural gas (G20)
CO₂ at high rate
More infoHide infoChecked in Calibration Mode at maximum rate, after running the boiler for several minutes, at the flue sampling point (MI 10.1). Section 7.2 says combustion is factory set and the air/gas ratio valve should not be adjusted at commissioning.
9.3% ± 0.2
CO₂ at low rate
More infoHide infoChecked in Calibration Mode at minimum rate (MI 10.1).
8.2% ± 0.2
Maximum CO
More infoHide infoFrom the Checking Combustion chart (MI 7.4), at the flue gas test point.
Max rate
< 350 ppm
Min rate
< 350 ppm
CO/CO₂ ratio
More infoHide infoFrom the Checking Combustion chart (MI 7.4). Sections 8.1 and 10.1 also say the ratio must be less than 0.004.
Max rate
< 0.004
Min rate
< 0.004
O₂
Not given in MI
Working inlet pressure
More infoHide infoAt the inlet gas pressure test point on the gas cock, boiler at maximum rate (MI 7.3, Fig. 47). Technical data gives inlet pressure 20 mbar, and fault finding (11.1) gives a preferred minimum gas pressure of 20 mbar. Fault finding chart H gives the natural gas supply pressure as greater than 10–11 mbar.
Appliance inlet
20 mbar
Gas rate at maximum
More infoHide infoTechnical data figure is after 10 minutes (MI 3.1). The commissioning range is measured with all other appliances and pilot lights off (MI 7.3). Technical data also gives 0.54 m³/h at minimum.
Technical data
1.63 m³/h
Commissioning
1.55–1.71 m³/h
Flue integrity
More infoHide infoAt the air inlet test point, boiler at maximum rate (MI 7.4).
O₂ ≥ 20.6%
CO₂ < 0.2%

From Comp No 7101615 - 04 (2/14)

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
Bermuda BBU 15 HE44-075-09NG

Source: Baxi Bermuda BBU 15 HE Condensing Back Boiler Unit Installation &amp; Servicing Instructions, Comp No 7101615 - 04 (2/14).

Sections: 1.1 Description; 3.1 Technical Data; 7.2 Commissioning the Boiler; 7.3 Check the Operational Gas Inlet Pressure; 7.4 Checking Combustion; 8.1 Annual Servicing; 10.1 Setting the Gas Valve (CO2 check); 11.1 Initial Fault Finding Checks; 11.0 Fault Finding chart H.

Spotted something wrong? Tell us.

Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.