Baxi Checked against MI

Baxi Duo-tec 2 Combi GA (24 GA, 28 GA, 33 GA, 40 GA)

Combi, natural gas and LPG

Combustion figures

FigureNatural gas (G20)LPG (G31)
CO₂ at high rate
More infoHide infoMI 14.1 gives one figure for all 3 fan speeds: ‘100’ (maximum), the Ignition Phase speed and ‘00’ (minimum). Combustion is factory set; MI 10.1 says no measurement of the combustion is needed at commissioning and not to adjust the air/gas ratio valve.
9.0% ± 0.710.5% ± 1.0
CO₂ at low rate
More infoHide infoSame figure as high rate (MI 14.1, all 3 fan speeds).
9.0% ± 0.710.5% ± 1.0
Maximum CO
More infoHide infoAt maximum and minimum rate (MI 10.2 commissioning flow chart). Not split by gas type.
< 350 ppm< 350 ppm
CO/CO₂ ratio
More infoHide infoAt maximum and minimum rate (MI 10.2 flow chart; MI 12.1 also says less than 0.004). Not split by gas type.
< 0.004< 0.004
O₂
Not given in MINot given in MI
Working inlet pressure
More infoHide infoMI 10.3 gives one figure for the inlet test point on the gas cock or the gas valve, at maximum rate: ‘AT LEAST 17mb ! (LPG - 37mb)’. Fault finding (MI 17.0, G) says at the gas valve: NG minimum 17 mbar, Propane minimum 37 mbar. Technical data (MI 4.1) gives nominal inlet pressure NG 20 mbar, Propane 37 mbar, point not stated. Initial fault finding checks (MI 17.1) say the preferred minimum gas pressure is 20 mbar (NG), 37 mbar (LPG).
Appliance inlet
At least 17 mbar
Gas valve test point
At least 17 mbar
Appliance inlet
At least 37 mbar
Gas valve test point
At least 37 mbar
Gas rate at maximum
More infoHide infoAfter 10 minutes (MI 4.1). Same figures in MI 10.3, measured with other appliances and pilots off.
24 GA
2.54 m³/h
28 GA
2.96 m³/h
33 GA
3.49 m³/h
40 GA
4.23 m³/h
24 GA
1.92 kg/h
28 GA
2.25 kg/h
33 GA
2.64 kg/h
40 GA
3.2 kg/h
Flue integrity
More infoHide infoAt the air inlet test point, boiler at maximum rate (MI 10.2 flow chart).
O₂ ≥ 20.6%
CO₂ < 0.2%
O₂ ≥ 20.6%
CO₂ < 0.2%

From Comp No. 7206334 - 09 (9/14)

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
Duo-tec 2 Combi 24 GA47-075-54Not stated
Duo-tec 2 Combi 28 GA47-075-55Not stated
Duo-tec 2 Combi 33 GA47-075-56Not stated
Duo-tec 2 Combi 40 GA47-075-57Not stated

Source: Baxi Duo-tec 2 Combi GA Range Installation &amp; Servicing Instructions, Comp No. 7206334 - 09 (9/14).

Sections: 4.1 Technical data; 10.1 Commissioning the boiler; 10.2 Checking the combustion - Chimney Sweep function; 10.3 Check the operational (working) gas inlet pressure & gas rate; 12.1 Performance safety check & annual servicing; 14.1 Checking the combustion; 14.2 Calibration function; 14.3 Adjusting the CO2; 17.0 Fault finding (G).

Spotted something wrong? Tell us.

Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.