Baxi Duo-tec Combi ErP (24, 28, 33, 40, 28 LPG)

Combi, natural gas and LPG

Combustion figures

FigureNatural gas (G20)LPG (G31)
CO₂ at high rate
More infoHide infoChecked in calibration mode at maximum rate, at the flue sampling test point, after running the boiler for several minutes. Case position not stated in MI. If CO₂ is reset at one rate, recheck the other rate.
8.7% ± 0.210% ± 0.2
CO₂ at low rate
More infoHide infoChecked in calibration mode at minimum rate (display reads 0).
8.4% ± 0.29.8% ± 0.2
Maximum CO
More infoHide infoAt both maximum and minimum rate, at the flue gas test point (commissioning flow chart, MI 10.2). The flow chart isn’t split by gas type.
< 350 ppm< 350 ppm
CO/CO₂ ratio
More infoHide infoAt both maximum and minimum rate (MI 10.2). MI 12.1 and 14.1 also say it must be less than 0.004.
< 0.004< 0.004
O₂
Not given in MINot given in MI
Working inlet pressure
More infoHide infoNG: the gas valve minimum is from fault finding chart I (MI 17.0), which doesn’t name the gas type. Technical data (MI 4.1) gives NG inlet pressure 20 mbar, and MI 17.1 says the preferred minimum gas pressure is 20 mbar; measurement point not stated in MI for either. MI 10.3 says to check at the inlet gas pressure test point on the gas valve at maximum rate, but gives no figure there. LPG (propane G31, MI 18.0): Measurement point not stated in MI.
Gas valve test point
Minimum 17 mbar
37 mbar
Gas rate at maximum
More infoHide infoAfter 10 minutes (MI 4.1). MI 10.3.8 gives the same NG figures, measured with other appliances and pilot lights off. LPG is the 28 LPG model only, propane G31 (MI 18.0).
24
2.61 m³/h
28
3.1 m³/h
33
3.6 m³/h
40
4.36 m³/h
2.25 kg/h
Flue integrity
More infoHide infoAt the air inlet test point, boiler at maximum rate (MI 10.2).
O₂ ≥ 20.6%
CO₂ < 0.2%
O₂ ≥ 20.6%
CO₂ < 0.2%

From 7219665 - 02 (10/15)

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
Duo-tec 24 Combi ErP47-075-96NG
Duo-tec 28 Combi ErP47-075-97NG
Duo-tec 33 Combi ErP47-075-99NG
Duo-tec 40 Combi ErP47-077-03NG
Duo-tec 28 LPG Combi ErP47-075-98LPG

Source: Baxi Duo-tec Combi 24 - 28 - 33 - 40, 28 LPG Installation and Service Manual, 7219665 - 02 (10/15).

Sections: 4.1 Technical data; 10.1 Commissioning the boiler; 10.2 Checking combustion; 10.3 Check the operational (working) gas inlet pressure; 12.1 Annual servicing; 14.1 Setting the gas valve (CO2 check); 17.0 Fault finding (chart I); 17.1 Initial fault finding checks; 18.0 LPG model supplement.

Spotted something wrong? Tell us.

Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.