Baxi Checked against MI

Baxi EcoBlue Plus Combi (24, 28, 33)

Combi, natural gas

Combustion figures

FigureNatural gas (G20)
CO₂ at high rate
More infoHide infoChecked after running the boiler for several minutes in chimney sweep mode, case front panel fitted. The valve is checked and set at maximum DHW input.
8.7% ± 0.2
CO₂ at low rate
More infoHide infoChecked at minimum input in chimney sweep mode. If CO₂ is reset at one rate, recheck the other.
8.4% ± 0.2
Maximum CO
More infoHide infoAt maximum DHW input and at minimum input, at the flue gas test point.
< 350 ppm
CO/CO₂ ratio
More infoHide infoAt maximum DHW input and at minimum input.
< 0.004
O₂
Not given in MI
Working inlet pressure
More infoHide infoFrom Fig. 41a. At the gas meter: 19–23 mbar. The text of 7.5.1 and fault finding chart G say the working pressure at the gas cock test point must be at least 17 mbar, while Fig. 41a gives 18–22 mbar there. 11.2 says the preferred minimum is 20 mb. Checked at maximum rate. Permissible pressure drop across system pipework ≤ 1 mbar.
Appliance inlet
18–22 mbar
Gas valve test point
17–21 mbar
Gas rate at maximum
More infoHide infoNatural gas (G20), after 10 minutes, with all other appliances and pilot lights off.
24
2.61 m³/h
28
3.05 m³/h
33
3.59 m³/h
Flue integrity
More infoHide infoAt the air inlet test point, boiler at maximum rate.
O₂ ≥ 20.6%
CO₂ < 0.2%

From 7219706 - 03 (09/16)

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
EcoBlue Plus 24 Combi ErP47-077-08NG
EcoBlue Plus 28 Combi ErP47-077-09NG
EcoBlue Plus 33 Combi ErP47-077-10NG

Source: Baxi EcoBlue Plus Combi 24 - 28 - 33 Installation and Service Manual, 7219706 - 03 (09/16).

Sections: 3.1 Technical Data; 7.4.1 Checking Combustion - Chimney Sweep Mode; 7.5.1 Check the Operational (Working Gas Inlet Pressure & Gas Rate); 10.1 General; 10.3.25 Setting the Gas Valve (CO₂ Check); 11.2 Fault Finding.