Baxi Checked against MI

Baxi EcoBlue System (12, 15, 18, 24, 28, 32)

System boiler, natural gas

Combustion figures

FigureNatural gas (G20)
CO₂ at high rate
More infoHide infoIn chimney sweep mode at maximum heating input, after running the boiler for several minutes, with the case front panel fitted.
8.7% ± 0.2
CO₂ at low rate
More infoHide infoIn chimney sweep mode at minimum input. If CO₂ is reset at one rate, recheck the other.
8.4% ± 0.2
Maximum CO
More infoHide infoFrom the commissioning flow chart. CO and ratio are measured at maximum DHW input and minimum input.
Max rate
<350 ppm
Min rate
<350 ppm
CO/CO₂ ratio
<0.004
O₂
Not given in MI
Working inlet pressure
More infoHide infoAt the gas meter: 19–23 mbar (Fig. 41a). Boiler at maximum rate. The text in 7.5.1 and the fault finding chart say at least 17 mbar at the gas cock test point, while Fig. 41a shows 18–22 mbar at the gas cock. Dynamic (nominal) inlet pressure in the technical data: 20 mbar.
Appliance inlet
18–22 mbar
Gas valve test point
17–21 mbar
Gas rate at maximum
More infoHide infoNatural gas G20, after 10 minutes, with all other appliances and pilot lights off.
12
1.27 m³/h
15
1.58 m³/h
18
1.9 m³/h
24
2.54 m³/h
28
2.96 m³/h
32
3.38 m³/h
Flue integrity
More infoHide infoAt the air inlet test point, boiler at maximum rate.
O₂ ≥ 20.6%
CO₂ < 0.2%

From 7212140 - 04 (09/14)

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
Baxi EcoBlue 12 System41-077-95NG
Baxi EcoBlue 15 System41-077-96NG
Baxi EcoBlue 18 System41-077-97NG
Baxi EcoBlue 24 System41-077-98NG
Baxi EcoBlue 28 System41-077-99NG
Baxi EcoBlue 32 System41-470-01NG

Source: Baxi EcoBlue System 12 - 15 - 18 - 24 - 28 - 32 Installation and Service Manual, 7212140 - 04 (09/14).

Sections: 3.1 Technical Data; 7.4.1 Check Combustion - Chimney Sweep Mode; 7.5.1 Check the Operational (Working Gas Inlet Pressure & Gas Rate); 10.1 General; 10.3.20 Setting the Gas Valve (CO₂ Check); 11.2 Fault Finding; 14.1 32 Model Supplement.