Baxi Platinum Combi ErP (24, 28, 33, 40)

Combi, natural gas

Combustion figures

FigureNatural gas (G20)
CO₂ at high rate
More infoHide infoChecked in Calibration Mode at maximum rate after running the boiler for several minutes, at the flue adaptor test point (MI 14.1).
8.7% ± 0.2
CO₂ at low rate
More infoHide infoChecked in Calibration Mode at minimum rate, after checking at maximum (MI 14.1).
8.4% ± 0.2
Maximum CO
More infoHide infoAt both maximum and minimum rate, at the flue gas test point (MI 10.2 flow chart).
< 350 ppm
CO/CO₂ ratio
More infoHide infoAt both maximum and minimum rate (MI 10.2). MI 12.1 and 14.1 also say less than 0.004.
< 0.004
O₂
Not given in MI
Working inlet pressure
More infoHide infoMeasured at maximum rate in Calibration Mode; MI 10.4 says it must be at least 17 mbar. At the gas meter: 19–23 mbar. Permissible pressure drop across system pipework ≤ 1 mbar. Technical data (MI 4.1) gives inlet pressure 20 mbar (natural gas G20) without saying where it is measured.
Gas valve test point
17–21 mbar
Gas rate at maximum
More infoHide infoNatural gas G20, after 10 minutes (MI 4.1). Measure with other appliances and pilot lights off (MI 10.4).
24
2.61 m³/h
28
3.1 m³/h
33
3.6 m³/h
40
4.36 m³/h
Flue integrity
More infoHide infoAt the air inlet test point, boiler at maximum rate (MI 10.2 flow chart).
O₂ ≥ 20.6%
CO₂ < 0.2%

From 7647627 - 02 (9/16)

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
Platinum 24 Combi ErP47-077-04NG
Platinum 28 Combi ErP47-077-05NG
Platinum 33 Combi ErP47-077-06NG
Platinum 40 Combi ErP47-077-07NG

Source: Baxi Platinum Combi 24 - 28 - 33 - 40 Installation and Service Manual (Gas Fired Wall Mounted Condensing Combination Boiler), 7647627 - 02 (9/16).

Sections: 4.1 Technical Data; 10.1 Commissioning the Boiler; 10.2 Checking Combustion; 10.4 Check the Operational (Working) Gas Inlet Pressure; 12.1 Annual Servicing; 14.1 Setting the Gas Valve (CO2 check).

Spotted something wrong? Tell us.

Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.