Baxi Checked against MI

Baxi Platinum Combi HE A (24, 28, 33, 40 HE A)

Combi, natural gas

Combustion figures

FigureNatural gas (G20)
CO₂ at high rate
More infoHide infoMeasured at the flue adaptor test point in Calibration Mode at maximum rate, after running the boiler for several minutes. Same figure in 13.1 and 15.1.
8.7% ± 0.2
CO₂ at low rate
8.4% ± 0.2
Maximum CO
Not given in MI
CO/CO₂ ratio
Less than 0.004
O₂
Not given in MI
Working inlet pressure
More infoHide infoMeasurement point not stated in MI. Technical data gives inlet pressure 20 mbar; 11.3 says the gas supply pressure should be 20 mb; 18.1 says the preferred minimum gas pressure is 20 mbar. The fault finding chart (18.0, chart I) says to check the gas supply pressure is greater than 10 – 11 mbar.
20 mbar
Gas rate at maximum
More infoHide infoNatural gas G20, after 10 minutes, with other appliances and pilot lights off. 11.3 calls these approximate values.
24
2.61 m³/h
28
3.1 m³/h
33
3.6 m³/h
40
4.36 m³/h

From UK Comp No 5121651 - Iss 6 - 8/09

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
Baxi Platinum Combi 24 HE A47-075-31NG
Baxi Platinum Combi 28 HE A47-075-32NG
Baxi Platinum Combi 33 HE A47-075-33NG
Baxi Platinum Combi 40 HE A47-075-34NG

Source: Baxi Platinum Combi HE A Range installation & servicing instructions, UK Comp No 5121651 - Iss 6 - 8/09.

Sections: 4.1 Technical data; 11.3 Checking; 13.1 Annual servicing; 15.1 Checking the CO₂; 18.1 Initial fault finding checks; 18.0 Fault finding chart I.

Spotted something wrong? Tell us.

Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.