Baxi Checked against MI

Baxi Platinum+ 40 Combi (40)

Combi, natural gas

Combustion figures

FigureNatural gas (G20)
CO₂ at high rate
More infoHide infoChecked in Calibration Mode at maximum rate, after running the boiler for several minutes, at the flue adaptor test point.
8.7% ± 0.2
CO₂ at low rate
More infoHide infoChecked in Calibration Mode at minimum rate. If CO₂ is reset at one rate, recheck it at the other.
8.4% ± 0.2
Maximum CO
More infoHide infoAt both maximum and minimum rate (commissioning flow chart, section 10.2).
< 350 ppm
CO/CO₂ ratio
More infoHide infoAt both maximum and minimum rate (section 10.2). Sections 12.1 and 14.1 give the same limit.
< 0.004
O₂
Not given in MI
Working inlet pressure
More infoHide infoBoiler at maximum rate in Calibration Mode; section 10.3 says it must be at least 17 mbar. At the gas meter: 19–23 mbar. Technical data gives a nominal inlet pressure of 20 mbar. Permissible pressure drop across system pipework ≤ 1 mbar.
Gas valve test point
17–21 mbar
Gas rate at maximum
More infoHide infoTechnical data: after 10 minutes. Measure with other appliances and pilot lights off.
4.36 m³/h
Flue integrity
More infoHide infoAt the air inlet test point, boiler at maximum rate, case front panel fitted.
O₂ ≥ 20.6%
CO₂ < 0.2%

From 7734477-01 (7/19)

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
Platinum+ 40 Combi47-077-41NG

Source: Baxi Platinum+ 40 Combi Installation and Service Manual, 7734477-01 (7/19).

Sections: 4.1 Technical data; 10.1 Commissioning the boiler; 10.2 Checking combustion; 10.3 Check the operational (working) gas inlet pressure; 12.1 Annual servicing; 14.1 Setting the gas valve (CO2 check).

Spotted something wrong? Tell us.

Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.