Baxi Solo HE heat only (12 HE, 15 HE, 18 HE, 24 HE, 30 HE)

Heat only, natural gas

Combustion figures

FigureNatural gas (G20)
CO₂ at high rate
More infoHide infoRate not stated in MI: it gives one CO₂ level for all models, so it is shown at both rates. Check at the flue sampling point. No adjustment of the gas valve is permissible; if the level is higher, the MI says to call Baxi Technical Enquiries.
9% ± 1%
CO₂ at low rate
More infoHide infoRate not stated in MI: same single CO₂ level as high rate.
9% ± 1%
Maximum CO
Not given in MI
CO/CO₂ ratio
More infoHide infoCheck at the flue sampling point.
Up to a maximum of 0.004
O₂
Not given in MI
Working inlet pressure
More infoHide infoCheck at the inlet tapping of the gas valve with the system cold and all controls calling for heat. Do not check at the outlet test point.
Gas valve test point
Min 18.1 mbar, Max 22.5 mbar
Gas rate at maximum
More infoHide info2H, G20, 20 mbar, after 10 minutes. The 30 HE is factory set below its maximum and can be altered (MI section 10.8).
12 HE
1.34 m³/h
15 HE
1.64 m³/h
18 HE
1.94 m³/h
24 HE
2.31 m³/h
30 HE
2.95 m³/h

From Comp No 5120309 - Iss 3 - 7/07

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
Baxi Solo 12 HE41-075-50NG
Baxi Solo 15 HE41-075-46NG
Baxi Solo 18 HE41-075-51NG
Baxi Solo 24 HE41-075-45NG
Baxi Solo 30 HE41-075-44NG

Source: Baxi Solo HE Range installation & servicing instructions, Comp No 5120309 - Iss 3 - 7/07.

Sections: 4.0 Technical Data; 12.1 Commissioning the Boiler; 14.1 Annual Servicing; 15.8 Gas Valve.

Spotted something wrong? Tell us.

Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.