British Gas ICS1 system (ZSBR 7-28, ZSBR 11-28)

System boiler, natural gas and LPG

Combustion figures

FigureNatural gas (G20)LPG (G31)
CO₂ at high rate
More infoHide infoAt max. rated heat output, set with service function 2.0 Operating mode on Max. No tolerance given in MI. Same figures in Table 2 (MI 1.9) and Table 14 (MI 8.1).
9.2%10.8%
CO₂ at low rate
More infoHide infoAt min. rated heat output, set with service function 2.0 Operating mode on Min. No tolerance given in MI.
8.8%10.5%
Maximum CO
Not given in MINot given in MI
CO/CO₂ ratio
Not given in MINot given in MI
O₂
Not given in MINot given in MI
Working inlet pressure
More infoHide infoMeasured at the gas supply pressure testing point (item 7, on the gas valve). The MI says natural gas boilers must not be run below 18 mbar or above 24 mbar (nominal 20 mbar), and LPG boilers must not be run if the supply pressure is not 37 mbar. MI 5.1 words the LPG figure as at the inlet to the appliance.
Gas valve test point
18–24 mbar
Gas valve test point
37 mbar
Gas rate at maximum
More infoHide infoAfter 10 minutes from lighting. NG G20 (CVnet 34.02 MJ/m³), LPG (CVnet 88 MJ/m³).
2.9 m³/h2.1 kg/h
Flue integrity
More infoHide infoAt the combustion air testing point (234.1), in chimney sweep mode, for C13 or C33 flue systems. The MI says O₂ must not be less than 20,6% and CO₂ must not exceed 0,2%.
O₂ ≥ 20.6%
CO₂ ≤ 0.2%
O₂ ≥ 20.6%
CO₂ ≤ 0.2%

From 6 720 610 603 GB (03.02)

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
ZSBR 7-28 ICS141-108-04NG
ZSBR 11-28 propaneNot added yetLPG

Source: ICS1 Installation and Servicing Instructions, wall mounted condensing boiler for central heating, 6 720 610 603 GB (03.02).