Glow-worm Betacom 4 combi (24c -A, 30c -A)

Combi, natural gas

Combustion figures

FigureNatural gas (G20)
CO₂ at high rate
More infoHide infoCheck programme P.01 set to 100, wait 5 minutes for a stable reading, measure at the flue gas analysis point. The check figure (MI 7.9.5 and 11.4) is given for front casing on / front casing off. The setting figure is the CO₂ at full load in the Setting the CO₂ value table (MI 11.5); the text there says the value is with the front casing removed, while the table heading says front casing on / front casing off.
Check
9.2 ±1 %
Setting
9.2 ±0.2 %
CO₂ at low rate
Not given in MI
Maximum CO
More infoHide infoThe MI gives two different limits: ≤ 250 ppm at full load in the Setting the CO₂ value table (MI 11.5), and less than 350 ppm at maximum and minimum rate in the combustion chart (Appendix I). One box in the chart (after checking seals) says less than 335 ppm.
Setting table, full load
≤ 250 ppm
Combustion chart, max and min rate
less than 350 ppm
CO/CO₂ ratio
More infoHide infoThe MI gives two different limits: ≤ 0.0027 in the Setting the CO₂ value table (MI 11.5), and less than 0.004 at maximum and minimum rate in the combustion chart (Appendix I).
Setting table, full load
≤ 0.0027
Combustion chart, max and min rate
less than 0.004
O₂ at high rate
More infoHide infoO₂ at full load, from the Setting the CO₂ value table (MI 11.5).
4.5 ±1.8 vol. %
O₂ at low rate
Not given in MI
Working inlet pressure
More infoHide infoMeasured at the measuring nipple on the gas isolator cock, boiler at full load (check programme P.01 with an eBUS controller, or P.03 without). MI prints 1.7 ... 2 kPa (17.0 ... 20 mbar). Technical data gives G20 gas supply pressure 20 mbar.
Appliance inlet
17.0–20 mbar
Gas rate at maximum
More infoHide infoGas flow at P max, hot water (G20), from Technical data. MI 7.9.1 also gives a table of gas rates by the Qnw on the data plate, measured at the gas meter after 5 minutes on P.01: for 24.7 kW nominal 2.61 m³/h (+5% 2.74, −10% 2.35); for 30.6 kW nominal 3.24 m³/h (+5% 3.40, −10% 2.92).
24c -A
2.6 m³/h
30c -A
3.2 m³/h
Flue integrity
More infoHide infoAt the air inlet test point, boiler at maximum rate (combustion chart, Appendix I).
O₂ ≥ 20.6%
CO₂ < 0.2%

From 0020238424_02 &ndash; 15.11.2017

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
Betacom 4 24c -A (H-GB)47-019-52NG
Betacom 4 30c -A (H-GB)47-019-53NG

Source: Glow-worm Betacom 4 24c -A, 30c -A installation and maintenance instructions, 0020238424_02 &ndash; 15.11.2017.

Sections: 2.3 Validity of the instructions; 7.9.1 Checking the gas flow rate; 7.9.2 Checking the gas connection pressure (gas flow pressure); 7.9.3 Checking the leak-tightness of the flue gas installation and flue gas recirculation; 7.9.5 Checking the CO₂ content; 11.4 Checking the CO₂ content; 11.5 Setting the CO₂ content; Appendix A Check programmes; Appendix I Combustion chart; Appendix K Technical data.

Spotted something wrong? Tell us.

Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.