Glow-worm Betacom combi (24a, 28a)

Combi, natural gas (convertible to LPG)

Combustion figures

FigureNatural gas (G20)LPG (G31)
CO₂ at high rate
More infoHide infoBoiler forced to maximum with test mode P.01 set to HI, wait about 5 minutes for a stable reading, at the combustion analyser sample point on the flue. Case on is the check figure and case off is the setting figure (MI 19.3.3); the technical data (MI 5) calls this rate Qmax DHW. The manual contradicts itself: the gas conversion table (MI 17.1.2) gives the case on and case off figures the other way round (G20 case ON 9 ± 0.2 %, case OFF 9.2 ± 0.3 %; G31 case ON 10.1 ± 0.2 %, case OFF 10.3 ± 0.3 %). For LPG case off, the technical data gives ± 0.3% and MI 19.3.3 gives ± 0.2%. MI 19.3.3 prints the NG case off figure as 9 ± 0.2%.
Case on
9.2 ± 0.3%
Case off
9.0 ± 0.2%
Case on
10.3 ± 0.3%
Case off
10.1 ± 0.3% (MI 5) or 10.1 ± 0.2% (MI 19.3.3)
CO₂ at low rate
More infoHide infoAt Qmin. Given in the technical data (MI 5) only.
Case on
8.9 ± 0.3%
Case off
8.7 ± 0.2%
Case on
9.8 ± 0.3%
Case off
9.6 ± 0.2%
Maximum CO
Not given in MINot given in MI
CO/CO₂ ratio
More infoHide infoSafe combustion can only be verified by measuring the CO/CO₂ ratio; it must not exceed this value (MI 19.3.1, 19.3.3).
0.0040.004
O₂
Not given in MINot given in MI
Working inlet pressure
More infoHide infoNominal supply pressure, checked at the gas service isolation valve test point with all other gas appliances running (MI 12.6.1). The technical data (MI 5) gives the same inlet pressures without saying where they are measured. MI 12.6.1 adds that maximum heat input can be achieved at an inlet pressure down to 15 mbar.
Appliance inlet
20 mbar
Appliance inlet
37 mbar
Gas rate at maximum
More infoHide infoApproximate, at least 10 minutes after the burner has lit from cold, checked at the gas meter (MI 12.6.2). These match the maximum DHW gas flow rate in the technical data (MI 5), which also gives maximum heating gas flow rate: NG 24a 1.96, 28a 2.64 m³/h; LPG 24a 1.44, 28a 1.94 kg/h.
24a
2.54 m³/h
28a
2.96 m³/h
24a
1.87 kg/h
28a
2.17 kg/h

From 0020105022_01 - 12/10

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
Betacom 24a47-019-13NG
Betacom 28a47-019-14NG

Source: Glow-worm Betacom 24a, Betacom 28a Installation and Servicing, 0020105022_01 - 12/10.

Sections: 5 Technical data; 12.6 Gas rates; 12.6.1 Operational gas inlet pressure; 12.6.2 Gas rate; 14 Installation settings (test modes); 17.1.2 Adjusting the maximum power setting; 19.3 Combustion check and setting the air/gas ratio valve.

Spotted something wrong? Tell us.

Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.