Glow-worm Compact combi (24c-AS/1, 28c-AS/1)

Combi, natural gas and LPG

Combustion figures

FigureNatural gas (G20)LPG (G31)
CO₂ at high rate
More infoHide infoAt full load, check programme P.01, after at least 5 minutes. The MI contradicts itself on the case-on tolerance: section 9.6.5 (commissioning check) gives NG 9.2 ±1 % and LPG 10.6 ±0.5 %, while section 12.2 (checking and setting) gives ±0.3 for both gases. Case-off figures are from section 12.2 only, which says to set the CO₂ with the front casing removed.
Case on
9.2 ±0.3 vol. % (MI 12.2) / 9.2 ±1 % (MI 9.6.5)
Case off
9.0 ±0.3 vol. %
Case on
10.6 ±0.3 vol. % (MI 12.2) / 10.6 ±0.5 % (MI 9.6.5)
Case off
10.4 ±0.3 vol. %
CO₂ at low rate
Not given in MINot given in MI
Maximum CO
More infoHide infoAt full load, case on or off (MI 12.2). The Benchmark commissioning flow chart (Appendix H) uses CO less than 350 ppm as its pass level, and prints 335 ppm in one of its boxes.
≤ 250 ppm≤ 250 ppm
CO/CO₂ ratio
More infoHide infoCase on or off (MI 12.2). The Benchmark commissioning flow chart (Appendix H) uses a ratio less than 0.004 as its pass level.
≤ 0.0027≤ 0.0024
O₂ at high rate
More infoHide infoAt full load (MI 12.2).
Case on
4.5 ±0.5 vol. %
Case off
4.9 ±0.5 vol. %
Case on
5.1 ±0.4 vol. %
Case off
5.4 ±0.4 vol. %
O₂ at low rate
Not given in MINot given in MI
Working inlet pressure
More infoHide infoMeasured at the test nipple on the gas valve, with the boiler at maximum in check programme P.01 (MI 9.6.4). The MI adds that, because it is measured at the gas valve, the permissible minimum may be 1 mbar (0.1 kPa) lower than the figure shown. Technical data gives the gas connection pressure as 20.0 mbar (NG) and 37.0 mbar (LPG).
Gas valve test point
17.0–25.0 mbar
Gas valve test point
25.0–45.0 mbar
Gas rate at maximum
More infoHide infoMeasured at the gas meter, case on, after at least 5 minutes in check programme P.01, for the maximum Qnw on the data plate (24 kW and 28 kW) (MI 9.6.3). The technical data (MI section 3) gives slightly different maximum gas flows for hot water: G20 2.54 m³/h (24c) and 2.96 m³/h (28c); G31 1.86 kg/h (24c) and 2.18 kg/h (28c).
24c-AS/1
2.53 m³/h (+5%: 2.66, –10%: 2.28)
28c-AS/1
2.95 m³/h (+5%: 3.10, –10%: 2.66)
24c-AS/1
0.98 m³/h (+5%: 1.03, –10%: 0.88)
28c-AS/1
1.15 m³/h (+5%: 1.21, –10%: 1.04)
Flue integrity
More infoHide infoAt the air inlet test point, boiler at maximum rate (Benchmark commissioning flow chart, Appendix H). Section 9.6.2 says to check for flue gas recirculation at the air analysis point on extended flues, but gives no figures.
O₂ ≥ 20.6%
CO₂ < 0.2%
O₂ ≥ 20.6%
CO₂ < 0.2%

From 0020313973_01 (05.02.2021)

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
Compact 24c-AS/1 (H-GB)47-019-63NG
Compact 28c-AS/1 (H-GB)47-019-64NG
Compact 24c-AS/1 (P-GB)47-019-65LPG
Compact 28c-AS/1 (P-GB)47-019-66LPG

Source: Glow-worm Compact 24c-AS/1, 28c-AS/1 installation and maintenance instructions, 0020313973_01 (05.02.2021).

Sections: 3 Technical data; 4 Notes on the documentation; 9.6.2 Checking the air/flue pipe/flue gas recirculation; 9.6.3 Checking the gas flow rate; 9.6.4 Checking the gas connection pressure/gas flow pressure; 9.6.5 Checking the CO₂ content; 12.2 Checking and setting the CO₂ content; Appendix E Check programmes; Appendix H Commissioning Flow Chart.

Spotted something wrong? Tell us.

Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.