Glow-worm Energy 35 Store combi (35 Store-A)

Store combi (integral 42 l cylinder), natural gas and LPG

Combustion figures

FigureNatural gas (G20)LPG (G31)
CO₂ at high rate
More infoHide infoCheck programme P.01 set to 100 (maximum). Wait 2 minutes for a stable reading, then measure at the flue gas analysis point. The MI gives CO₂ at this setting only.
Front casing fitted
9.2 ±0.3 %
Front casing removed
9 ±0.2 %
Front casing fitted
10.3 ±0.3 %
Front casing removed
10.1 ±0.2 %
CO₂ at low rate
Not given in MINot given in MI
Maximum CO
More infoHide infoThe combustion chart gives less than 350 ppm at maximum and minimum rate, but the re-check box (after checking seals) says less than 335 ppm. Both are shown as printed.
Combustion check
less than 350 ppm
Re-check after seals
less than 335 ppm
Combustion check
less than 350 ppm
Re-check after seals
less than 335 ppm
CO/CO₂ ratio
More infoHide infoAt maximum and minimum rate, from the combustion chart.
Less than 0.004Less than 0.004
O₂
Not given in MINot given in MI
Working inlet pressure
More infoHide infoNominal figures only: the MI gives no permissible range. Measured at the measuring nipple on the gas valve with the boiler at full load (check programme P.01). Section 6.10.2 labels the 37 mbar figure G31 natural gas mode; the technical data gives it as G31 gas supply pressure.
Gas valve test point
20 mbar
Gas valve test point
37 mbar
Gas rate at maximum
More infoHide infoGas flow at P max. in hot water mode (G20).
3.77 m³/hNot given in MI
Flue integrity
More infoHide infoAt the air inlet test point, boiler at maximum rate (combustion chart).
O₂ ≥ 20.6%
CO₂ < 0.2%
O₂ ≥ 20.6%
CO₂ < 0.2%

From 0020201109_01 (19.08.2015)

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
Energy 35 Store-A47-019-37NG

Source: Glow-worm Energy 35 Store-A (H-GB) installation and maintenance instructions, 0020201109_01 (19.08.2015).

Sections: 3.2 Gas Council number; 6.10.1 Checking the leak-tightness of the flue gas system; 6.10.2 Checking the gas flow pressure; 6.10.4 Checking the CO₂ content; 6.10.5 Setting the CO₂ content; 9.3 Gas conversion procedure; B Check programmes; I Technical data; K Combustion chart.