Glow-worm Checked against MI

Glow-worm sxi system (18sxi, 30sxi)

System boiler, natural gas (30sxi LPG conversion)

Combustion figures

FigureNatural gas (G20)LPG (G31)
CO₂ at high rate
More infoHide infoTable 2 and 11.5 don’t say which rate. 12.6 gives these figures at maximum fan speed (service potentiometer fully clockwise: display 57 ±1 for 30sxi, 41 ±1 for 18sxi). The manual contradicts itself on the case-on figures: NG case on is 9.3% +0.3 −0.5 in Table 2 and 11.5 but 9.1% +0.3 −0.5 in 12.6; LPG case on is 10.7% +0.3 −0.8 in 11.5 but 10.7% +0.3 −0.7 in 12.6. 12.6 also says the final maximum rate recheck should be “9.1+0.2-0.5 ± 0.2%”. LPG is the 30sxi only, after conversion. The LPG conversion procedure (section 11) says that after setting combustion, with the service potentiometer turned fully anti-clockwise (normal running), CO₂ should stay between 9.8% and 10.8%.
Case off
9.1% +0.2 −0.5
Case on
9.3% +0.3 −0.5 (Table 2 and 11.5) or 9.1% +0.3 −0.5 (12.6)
Case off
10.5% +0.3 −0.7
Case on
10.7% +0.3 −0.8 (11.5) or 10.7% +0.3 −0.7 (12.6)
CO₂ at low rate
More infoHide infoService potentiometer at the mid-point (3 o’clock): fan 1200 ±100 rpm, display flashes ‘12’. Measured with the front and inner casing panels off; MI gives no case-on figure at low rate. NG from 12.6; LPG (30sxi only) from the LPG conversion procedure in section 11, step 9.
9.1% +0.2 −0.510.5% ± 0.2%
Maximum CO
Not given in MINot given in MI
CO/CO₂ ratio
Not given in MINot given in MI
O₂
Not given in MINot given in MI
Working inlet pressure
More infoHide infoNG: 1.3 says 20 mbar at the boiler; 11.5 says 20 mb at the gas valve pressure test point with the boiler at full rate. No tolerance given. LPG: section 11 and 11.5 say the supply pressure should be 37 mb. Measurement point not stated in MI.
Appliance inlet
20 mbar
Gas valve test point
20 mbar
37 mbar
Gas rate at maximum
More infoHide infoApproximate, after 10 minutes from cold (Table 2). At minimum: 0.53 m³/h for both sizes. Check with the gas meter test dial at least 10 minutes after the burner has lit, with all other gas appliances off (11.5).
18sxi
2.00 m³/h
30sxi
3.0 m³/h
Not given in MI

From 0020008155A.02.05

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
18sxi41-047-72NG
30sxi41-047-62NG
30sxi converted to LPG41-047-62LPG

Source: Glow-worm 18sxi, 30sxi High Efficiency Condensing System Boiler Instructions for Use, Installation and Servicing, 0020008155A.02.05.

Sections: 1.1 Important notice; 1.3 Gas supply; 1.4 Technical data (Diagram 1.2, Table 2); 11 Commissioning: LPG conversion (30sxi only); 11.5 Testing - Gas; 12.6 Combustion check.