Glow-worm Checked against MI

Glow-worm Ultimate 3 combi (30c, 35c)

Combi, natural gas

Combustion figures

FigureNatural gas (G20)
CO₂ at high rate
More infoHide infoCheck programme P.01 set to 100 (full load), reading taken once stable (about 5 minutes), at the flue gas analysis point. The MI gives 9.2 ±1 % as the acceptable checking range (7.9.5 and 11.3) and 9.2 ±0.2 % as the figure to set to if adjustment is needed (11.4). Both tables are headed front casing removed/installed; 11.4 says the set value is with the front casing removed.
Check
9.2 ±1 %
Set to
9.2 ±0.2 %
CO₂ at low rate
Not given in MI
Maximum CO
More infoHide infoGiven as CO at full load (11.4). The generic combustion chart in Appendix J uses CO less than 350 ppm at maximum and minimum rate (one box in the chart says 335 ppm).
≤ 250 ppm
CO/CO₂ ratio
More infoHide infoFrom the 11.4 table, alongside CO at full load. The generic combustion chart in Appendix J uses a ratio less than 0.004 at maximum and minimum rate.
≤ 0.0027
O₂ at high rate
More infoHide infoGiven as O₂ at full load in the Setting the CO₂ value table (11.4).
4.5 ±1.8 vol. %
O₂ at low rate
Not given in MI
Working inlet pressure
More infoHide infoPermissible connection pressure (G20), measured at the measuring nipple on the gas isolator cock with the boiler at full load (P.01 or P.03). Technical data gives G20 gas supply pressure as 20 mbar.
Appliance inlet
17.0–20 mbar
Gas rate at maximum
More infoHide infoGas flow at P max., hot water (G20), from Technical data. The gas flow rate table in 7.9.1 gives, by Qnw from the data plate: 30.6 kW 3.24 m³/h (+5% 3.40, −10% 2.92); 35.7 kW 3.78 m³/h (+5% 3.97, −10% 3.40). Measured at the gas meter with P.01 after at least 5 minutes.
30c
3.2 m³/h
35c
3.8 m³/h
Flue integrity
More infoHide infoAt the air inlet test point with the boiler at maximum rate (Appendix J combustion chart; 7.9.3).
O₂ ≥ 20.6%
CO₂ < 0.2%

From 0020239566_01 &ndash; 10.10.2016

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
Ultimate 3 30c47-019-55NG
Ultimate 3 35c47-019-57NG

Source: Glow-worm Ultimate 3 30c, 35c installation and maintenance instructions, 0020239566_01 &ndash; 10.10.2016.

Sections: 2.3 Applicability of the instructions; 7.9 Checking and adjusting the gas ratio setting; 7.9.1 Checking the gas flow rate; 7.9.2 Checking the gas connection pressure; 7.9.3 Checking the leak-tightness of the flue gas installation and flue gas recirculation; 7.9.5 Checking the CO₂ content; 11.3 Checking the CO₂ content; 11.4 Setting the CO₂ content; A Check programmes; J Combustion chart; L Technical data.

Spotted something wrong? Tell us.

Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.