Glow-worm Ultracom 2 sxi system (12sxi, 18sxi, 30sxi)

System boiler, natural gas, 18sxi and 30sxi convertible to LPG

Combustion figures

FigureNatural gas (G20)LPG (G31)
CO₂ at high rate
More infoHide infoSame for all sizes. Case on is the check figure and case off the setting figure (MI 18.3.3), read after about 5 minutes at maximum (test mode P.01 set to 100). The technical data (MI 5) agrees. The table in MI 16.1.2 (gas conversion) has case on and case off the other way round: NG case on 9 ± 0.2%, case off 9.2 ± 0.3%; LPG case on 10.1 ± 0.2%, case off 10.3 ± 0.3%. LPG figures are for 18sxi and 30sxi only: the MI says 12sxi can’t be converted to LPG.
Case on
9.2 ± 0.3%
Case off
9 ± 0.2%
Case on
10.3 ± 0.3%
Case off
10.1 ± 0.2%
CO₂ at low rate
More infoHide infoAt Qmin, from the technical data only (MI 5). Same for all sizes. LPG figures are for 18sxi and 30sxi only.
Case on
8.9 ± 0.3%
Case off
8.7 ± 0.2%
Case on
9.8 ± 0.3%
Case off
9.6 ± 0.2%
Maximum CO
Not given in MINot given in MI
CO/CO₂ ratio
More infoHide infoMust not be exceeded. Same for all sizes, checked at maximum rate (MI 18.3.3).
0.0040.004
O₂
Not given in MINot given in MI
Working inlet pressure
More infoHide infoNominal supply pressure, checked at the gas service isolation valve test point with all other gas appliances operating (MI 12.5.1). The MI says the safe nominal maximum heat input can be achieved at an inlet pressure down to 15 mbar.
Appliance inlet
20 mbar
Appliance inlet
37 mbar
Gas rate at maximum
More infoHide infoFrom the technical data (MI 5). The gas rates table in MI 12.5.2 (approx, after 10 mins from cold) gives the same for 12sxi but different maximums for the others: NG 18sxi 2.7 m³/h, 30sxi 3.77 m³/h; LPG 18sxi 1.98 kg/h, 30sxi 2.77 kg/h. The MI says 12sxi can’t be converted to LPG.
12sxi
1.3 m³/h
18sxi
1.96 m³/h
30sxi
3.24 m³/h
12sxi
Not given in MI
18sxi
1.44 kg/h
30sxi
2.37 kg/h

From 0020092785_02 - 05/10

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
Ultracom2 12sxi41-019-12NG
Ultracom2 18sxi41-019-13NG
Ultracom2 30sxi41-019-14NG

Source: Glow-worm Ultracom₂ sxi Installation and Servicing, 0020092785_02 - 05/10.

Sections: 2.3 Gas category; 5 Technical data; 12.5 Gas rates; 12.5.1 Operational gas inlet pressure; 12.5.2 Gas rate; 16.1.2 Adjusting the maximum power setting; 18.3.3 Maximum rate check and adjustment.