Glow-worm Checked against MI

Glow-worm Ultracom cx combi (24cx, 30cx)

Combi, natural gas (LPG by conversion)

Combustion figures

FigureNatural gas (G20)LPG (G31)
CO₂ at high rate
More infoHide infoFrom the burner % CO₂ tables in section 13 (and 12.9 for LPG). The MI uses the same table for maximum and minimum rate: check the reading against the Check column, and adjust to the Setting column if needed. Section 1 Boiler Specification gives a different NG figure: burner % CO₂ 9.3 nominal, case on and case off, for both sizes. Section 1 gives no LPG figure.
Check (case on)
8.5 to 9.6%
Setting (case off)
9.1% +0.2 / −0.5
24cx
check 9.2 to 10.2% (case on), setting 10.0% +0.0 / −0.9 (case off)
30cx
check 10.0 to 11.0% (case on), setting 10.5% +0.3 / −0.7 (case off)
CO₂ at low rate
More infoHide infoSame table as maximum rate. The MI says adjustment at minimum rate is very coarse: no more than 1/8 of a turn of the offset adjustment at a time, waiting 1 minute between adjustments.
Check (case on)
8.5 to 9.6%
Setting (case off)
9.1% +0.2 / −0.5
24cx
check 9.2 to 10.2% (case on), setting 10.0% +0.0 / −0.9 (case off)
30cx
check 10.0 to 11.0% (case on), setting 10.5% +0.3 / −0.7 (case off)
Maximum CO
Not given in MINot given in MI
CO/CO₂ ratio
More infoHide infoMust not exceed this value. If it does after servicing and adjustment, the MI says the appliance must be disconnected until the ratio is acceptable.
0.0040.004
O₂
Not given in MINot given in MI
Working inlet pressure
More infoHide infoMeasured at the gas service isolation valve test point with all other gas appliances operating, and the boiler at maximum heat input. The MI says the inlet pressure at the main gas valve can be up to 2 mbar less than the supply pressure at maximum heat input, and that the safe nominal maximum heat input can be achieved at an inlet pressure down to 15 mbar.
Appliance inlet
20 mbar (nominal)
Appliance inlet
37 mbar (nominal)
Gas rate at maximum
More infoHide infoApproximate, after 10 minutes from cold, from the gas rates table in 12.5. Section 1 Boiler Specification gives different NG figures, labelled Approximate CH max. gas rate after 10 mins from cold: 24cx 1.94 m³/h, 30cx 2.45 m³/h. The MI doesn’t say which demand the 12.5 table is for.
24cx
2.24 m³/h
30cx
2.80 m³/h
24cx
1.88 kg/hr
30cx
2.34 kg/hr

From 0020040955-04 09.09

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
Ultracom 24cx47-019-06NG
Ultracom 30cx47-019-07NG

Source: Glow-worm Ultracom 24cx, 30cx Installation and Servicing, 0020040955-04 09.09.

Sections: 1 Boiler Specification; 12.4 Initial Lighting; 12.5 Check the Gas Inlet Pressure and Gas Rate; 12.9 LPG Conversion; 13 Servicing: Combustion check and setting the air/gas ratio valve.

Spotted something wrong? Tell us.

Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.