Ideal Atlantic Combi (24, 30, 35)

Combi, natural gas

Combustion figures

FigureNatural gas (G20)
CO₂ at high rate
More infoHide infoTable 1 gives this as CO₂ content at Max. DHW.
24, 35
9.5% ± 0.7
30
9.3% ± 0.7
CO₂ at low rate
More infoHide infoTable 1 gives this as CO₂ content at Min. CH.
24, 30
8.8% ± 0.7
35
8.9% ± 0.7
Maximum CO
More infoHide infoAt maximum and minimum rate, at the flue gas sampling point, after readings stabilise (commissioning flowchart).
Less than 350 ppm
CO/CO₂ ratio
More infoHide infoAt maximum and minimum rate (commissioning flowchart). The servicing section gives the same limit written as 0.004: above it, clean the boiler.
Less than 0.0040
O₂
Not given in MI
Working inlet pressure
More infoHide infoChecked at maximum rate (hot tap fully open) at the inlet pressure test point on the gas service cock. The MI says the gas cock can reduce the pressure further when measured at its test point, by an amount that depends on heat input (see the gas cock pressure drop graph in MI section 1.8). Minimum meter outlet: 19 mbar. The MI also says the boiler can give full output at inlet pressures as low as 14 mbar.
Appliance inlet
18 mbar minimum
Gas rate at maximum
More infoHide infoMaximum DHW gas consumption (Table 3), checked at the gas meter at full DHW output with no other appliance in use. Maximum CH gas consumption is 2.512 m³/h (Table 2). Based on a gross CV of 38.7 MJ/m³.
24
2.512 m³/h
30
3.135 m³/h
35
3.657 m³/h
Flue integrity
More infoHide infoAt the air inlet test point, boiler at maximum rate, after readings stabilise (commissioning flowchart).
O₂ ≥ 20.6% or CO₂ ≤ 0.2%

From UIN 223483 A03 (July 2020)

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
Atlantic Combi 2447-349-81NG
Atlantic Combi 3047-349-82NG
Atlantic Combi 3547-349-83NG

Source: Atlantic combination boilers installation & servicing instructions, UIN 223483 A03 (July 2020).