Ideal Atlantic Combi (24, 30, 35)
Combi, natural gas
Combustion figures
| Figure | Natural gas (G20) |
|---|---|
CO₂ at high rate More infoHide infoTable 1 gives this as CO₂ content at Max. DHW. |
|
CO₂ at low rate More infoHide infoTable 1 gives this as CO₂ content at Min. CH. |
|
Maximum CO More infoHide infoAt maximum and minimum rate, at the flue gas sampling point, after readings stabilise (commissioning flowchart). | Less than 350 ppm |
CO/CO₂ ratio More infoHide infoAt maximum and minimum rate (commissioning flowchart). The servicing section gives the same limit written as 0.004: above it, clean the boiler. | Less than 0.0040 |
O₂ | Not given in MI |
Working inlet pressure More infoHide infoChecked at maximum rate (hot tap fully open) at the inlet pressure test point on the gas service cock. The MI says the gas cock can reduce the pressure further when measured at its test point, by an amount that depends on heat input (see the gas cock pressure drop graph in MI section 1.8). Minimum meter outlet: 19 mbar. The MI also says the boiler can give full output at inlet pressures as low as 14 mbar. |
|
Gas rate at maximum More infoHide infoMaximum DHW gas consumption (Table 3), checked at the gas meter at full DHW output with no other appliance in use. Maximum CH gas consumption is 2.512 m³/h (Table 2). Based on a gross CV of 38.7 MJ/m³. |
|
Flue integrity More infoHide infoAt the air inlet test point, boiler at maximum rate, after readings stabilise (commissioning flowchart). | O₂ ≥ 20.6% or CO₂ ≤ 0.2% |
From UIN 223483 A03 (July 2020)
Enter service mode for high and low rate
High rate
Steps not added yet. Follow the MI.
Low rate
Steps not added yet. Follow the MI.
Ending the test: follow the MI.
Models and GC numbers
| Model | GC number | Gas |
|---|---|---|
| Atlantic Combi 24 | 47-349-81 | NG |
| Atlantic Combi 30 | 47-349-82 | NG |
| Atlantic Combi 35 | 47-349-83 | NG |
Source: Atlantic combination boilers installation & servicing instructions, UIN 223483 A03 (July 2020).
Sections: 1.8 Gas supply; Table 1 General data; Tables 2 & 3 Performance data; 2.23 Commissioning and testing; 2.24 Initial lighting; 2.25 General checks; 3.1 Servicing; 6 Flue & integrity checks (flowchart and setting to maximum/minimum rate).
Spotted something wrong? Tell us.
Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.