Ideal Logic Heat² H heat only (H12, H15, H18, H24, H30)
Heat only, natural gas
Combustion figures
| Figure | Natural gas (G20) |
|---|---|
CO₂ at high rate More infoHide infoTable 1 General Data, CO₂ content (± 0.7), Max. CH. The table heads the sizes 12 kW to 30 kW. The air/gas ratio valve is factory set and must not be adjusted. |
|
CO₂ at low rate More infoHide infoTable 1 General Data, CO₂ content (± 0.7), Min. CH. |
|
Maximum CO More infoHide infoAt maximum and minimum rate, from the Benchmark CO and combustion ratio flowchart. Probe in the flue gas sampling point, readings allowed to stabilise. | Less than 350 ppm |
CO/CO₂ ratio More infoHide infoAt maximum and minimum rate (Benchmark flowchart). The servicing schedule (3.1) checks the ratio at maximum rate: above 0.004 go to the cleaning procedure, below 0.004 go to the check procedure. | Less than 0.0040 |
O₂ | Not given in MI |
Working inlet pressure More infoHide infoMI gives a minimum only, no range: a minimum permitted operating pressure of 18 mb will be delivered to the inlet of the appliance (1.9). The ignition lockout chart says gas pressure at the boiler inlet over 18 mbar. Gas supply 2H - G20 - 20 mbar (Table 1). Minimum meter outlet 19 mb. MI says the 1:1 gas valve gives full output at inlet pressures as low as 14 mb. Measured at the test point on the gas service cock, boiler at maximum rate. |
|
Gas rate at maximum More infoHide infoGas consumption, Table 2. Calculated with a calorific value of 38.7 MJ/m³ gross. At minimum: 0.500 m³/h (H12, H15, H18, H24), 0.623 m³/h (H30). |
|
Flue integrity More infoHide infoAt the air inlet (air sample) test point, boiler at maximum rate (Benchmark flowchart). MI wording: O₂ more than or equal to 20.6% OR CO₂ less than or equal to 0.2%. | O₂ ≥ 20.6% or CO₂ ≤ 0.2% |
From UIN 228298 A04 (October 2022)
Enter service mode for high and low rate
High rate
Steps not added yet. Follow the MI.
Low rate
Steps not added yet. Follow the MI.
Ending the test: follow the MI.
Models and GC numbers
| Model | GC number | Gas |
|---|---|---|
| Logic Heat² H12 | 41-860-10 | NG |
| Logic Heat² H15 | 41-860-11 | NG |
| Logic Heat² H18 | 41-860-12 | NG |
| Logic Heat² H24 | 41-860-13 | NG |
| Logic Heat² H30 | 41-860-14 | NG |
Source: Ideal Logic Heat² H12 H15 H18 H24 H30 Installation & Servicing, UIN 228298 A04 (October 2022).
Sections: Table 1 General Data; Table 2 Performance Data; Section 1 GC numbers (p. 7); 1.9 Gas Supply; 2.29 Commissioning and Testing; 2.30 Initial Lighting; 2.35 Accessing the Installer Mode; 3.1 Servicing Schedule; 4.3 L 02 Ignition Lockout; Section 6 Benchmark flowchart for CO level and combustion ratio check.
Spotted something wrong? Tell us.
Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.