Ideal Logic Max Heat H (12, 15, 18, 24, 30)
Heat only (regular), natural gas
Combustion figures
| Figure | Natural gas (G20) |
|---|---|
CO₂ at high rate More infoHide infoTable 1 CO₂ content (± 0.7), Max. CH. The MI gives no timing or case on/off condition here; the flowchart says to let readings stabilise before recording. The air/gas ratio valve is factory set and must not be adjusted during commissioning. |
|
CO₂ at low rate More infoHide infoTable 1 CO₂ content (± 0.7), Min. CH. |
|
Maximum CO More infoHide infoAt maximum and minimum rate (commissioning flowchart, MI p. 67). | Less than 350 ppm |
CO/CO₂ ratio More infoHide infoAt maximum and minimum rate (commissioning flowchart, MI p. 67). Section 3.1 Servicing schedule gives the same limit as 0.004: above it, carry out the cleaning procedure. | Less than 0.0040 |
O₂ | Not given in MI |
Working inlet pressure More infoHide infoSection 1.8: minimum permitted operating pressure of 18 mb at the appliance inlet, allowing 1 mb loss from a minimum meter outlet of 19 mb. Checked at maximum rate at the inlet pressure test point on the gas service cock. Table 1 gives the gas supply as 2H - G20 - 20 mbar. The MI also says the boiler can deliver full output at inlet pressures as low as 14 mb, and that the gas cock reduces the pressure measured at its test point (graph in Section 1.8). |
|
Gas rate at maximum More infoHide infoTable 2 gas consumption at maximum input. Calculated using a calorific value of 38.7 MJ/m³ gross. Check at the gas meter with no other appliance in use. |
|
Flue integrity More infoHide infoAt the air inlet test point, boiler at maximum rate. Where no air inlet test point is provided, check the flue visually instead. | O₂ ≥ 20.6% or CO₂ ≤ 0.2% |
From UIN 219010 A04 (February 2019)
Enter service mode for high and low rate
High rate
Steps not added yet. Follow the MI.
Low rate
Steps not added yet. Follow the MI.
Ending the test: follow the MI.
Models and GC numbers
| Model | GC number | Gas |
|---|---|---|
| Logic Max Heat H 12 | 41-796-17 | NG |
| Logic Max Heat H 15 | 41-796-18 | NG |
| Logic Max Heat H 18 | 41-796-19 | NG |
| Logic Max Heat H 24 | 41-796-20 | NG |
| Logic Max Heat H 30 | 41-796-21 | NG |
Source: Ideal Logic Max Heat H 12 15 18 24 30 Installation & Servicing, UIN 219010 A04 (February 2019).
Sections: Table 1 General data; Table 2 Performance data; 1.8 Gas supply; 2.25 Commissioning and testing; 2.27 General checks; 3.1 Servicing schedule; Flowchart for CO level and combustion ratio check (setting to maximum and minimum rate).
Spotted something wrong? Tell us.
Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.