Ideal Logic+ Heat (H12, H15, H18, H24, H30)
Heat only, natural gas
Combustion figures
| Figure | Natural gas (G20) |
|---|---|
CO₂ at high rate More infoHide infoTable 1 gives CO₂ at Max. CH and Min. CH, with a tolerance of ± 0.7. Measure at the flue gas sampling point and let the readings stabilise. The air/gas ratio valve is factory set and must not be adjusted. |
|
CO₂ at low rate |
|
Maximum CO More infoHide infoCheck at maximum and minimum rate, from the commissioning flowchart. Do not run the boiler with the front panel off. | Less than 350 ppm |
CO/CO₂ ratio More infoHide infoAt maximum and minimum rate, from the commissioning flowchart. The servicing schedule (MI 3.1) writes the same limit as 0.004: above it, carry out the cleaning procedure. | Less than 0.0040 |
O₂ | Not given in MI |
Working inlet pressure More infoHide infoCheck at maximum rate at the inlet pressure test point on the gas service cock. MI 1.8: minimum meter outlet 19 mbar; allowing 1 mbar loss across the pipework, 18 mbar minimum at the appliance inlet. The gas cock can reduce the reading at its test point further, depending on heat input (graph in MI 1.8). The 1:1 gas valve can give full output at inlet pressures as low as 14 mbar. Gas supply in Table 1: 2H - G20 - 20 mbar. |
|
Gas rate at maximum More infoHide infoFrom Table 2, calculated at a calorific value of 38.7 MJ/m³ gross. Check at the meter with the boiler at maximum output and no other appliance in use. |
|
Flue integrity More infoHide infoAt the air inlet test point, boiler at maximum rate. The MI flowchart passes the check if O₂ is 20.6% or more OR CO₂ is 0.2% or less. | O₂ ≥ 20.6% CO₂ ≤ 0.2% |
From UIN 215355 A10 (February 2019)
Enter service mode for high and low rate
High rate
Steps not added yet. Follow the MI.
Low rate
Steps not added yet. Follow the MI.
Ending the test: follow the MI.
Models and GC numbers
| Model | GC number | Gas |
|---|---|---|
| Logic+ Heat H12 | 41-750-82 | NG |
| Logic+ Heat H15 | 41-750-83 | NG |
| Logic+ Heat H18 | 41-750-84 | NG |
| Logic+ Heat H24 | 41-750-85 | NG |
| Logic+ Heat H30 | 41-750-86 | NG |
Source: Ideal Logic+ Heat H12 H15 H18 H24 H30 Installation & Servicing, UIN 215355 A10 (February 2019).
Sections: Table 1 General Data; Table 2 Performance Data; 1.8 Gas Supply; 2.25 Commissioning and Testing; 2.26 Initial Lighting; 2.27 General Checks; 2.29 Accessing the Installer Mode; 3.1 Servicing Schedule; 4.3 L2 Ignition Lockout; Flowchart for CO level and combustion ratio check on commissioning (MI p. 64-65).
Spotted something wrong? Tell us.
Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.