Vaillant ecoTEC pro combi (24, 28)

Combi, natural gas

Combustion figures

FigureNatural gas (G20)
CO₂ at high rate
More infoHide infoAfter 5 minutes in full load mode (test program P.1), measured at the flue gas analysis point. If adjustment is needed, set it to the front removed figure (MI 7.1.4).
Front closed
9.2% ± 1,0
Front removed
9.0% ± 1,0
CO₂ at low rate
Not given in MI
Maximum CO
More infoHide infoAt full load.
< 250 ppm
CO/CO₂ ratio
< 0,0031
O₂
Not given in MI
Working inlet pressure
More infoHide infoAt the reference test point (sealing screw marked in on the gas valve), measured at full load in test program P.1. The MI also asks for the gas pipework to be sized so 20 mbar is available at the boiler inlet at full flow rate (MI 4.9), the technical data gives the inlet gas working pressure required as 20 mbar with no measurement point (MI 2.1), and the fault finding checks say 20 mbar should be available at the gas valve (MI 8.1).
Gas valve test point
16–23 mbar
Gas rate at maximum
More infoHide infoNominal rate with the +5% and −10% tolerance limits (Table 5.1). Measured at the gas meter after at least 5 minutes in test program P.1, with all other gas appliances off. The technical data gives a rounded connected load at 15 °C and 1013 mbar: 24: 2.5, 28: 3.0 m³/h (MI 2.1).
24
2.49 m³/h (+5%: 2.61, −10%: 2.24)
28
3.03 m³/h (+5%: 3.18, −10%: 2.72)
Flue integrity
More infoHide infoChecked with the flue gas analyser at the air measure point; strongly recommended where the flue is longer than 2 m. If any CO or CO₂ is found, find and correct the flue gas leak or recirculation; if it can’t be corrected, don’t start the boiler (MI 5.9.1).
No CO or CO₂ in the fresh air

From 839592_12 GBIE 062010

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
ecoTEC pro 2447-044-36NG
ecoTEC pro 2847-044-30NG

Source: Instructions for installation and servicing ecoTEC, 839592_12 GBIE 062010.

Sections: 1.3 Introduction; 1.7 Gas council numbers; 2.1 Technical data; 4.9 Gas connection; 5.9.1 Checking for tightness of the flue gas installation and flue gas recirculation; 5.9.2 Checking the gas flow rate; 5.9.3 Checking the gas inlet working pressure; 7.1.3 Checking the CO2 concentration; 7.1.4 Adjusting the CO2 concentration (or the air ratio); 8.1 Logical fault finding procedure; 8.2 Test programs.