Vaillant Home Regular (12 -A, 15 -A, 18 -A, 25 -A, 30 -A)

Regular (heat only), natural gas

Combustion figures

FigureNatural gas (G20)
CO₂ at high rate
More infoHide infoAfter 5 minutes in full load mode (check programme P.01 set to 100). Set for Wobbe index 15 kWh/m³. When adjusting, set the case-off value.
Case on
9.2% ± 1.0
Case off
9.0% ± 1.0
CO₂ at low rate
Not given in MI
Maximum CO
More infoHide infoThe two figures come from different parts of the MI: the section 7.8 table gives ≤ 250 ppm in full load mode, while the combustion chart (Appendix J) uses less than 350 ppm at maximum and minimum rate. The chart’s recheck after checking seals says 335 ppm.
Full load (section 7.8)
≤ 250 ppm
Max and min rate (combustion chart)
Less than 350 ppm
CO/CO₂ ratio
More infoHide infoThe section 7.8 table gives ≤ 0.0027; the combustion chart (Appendix J) uses less than 0.004 at maximum and minimum rate.
Full load (section 7.8)
≤ 0.0027
Max and min rate (combustion chart)
Less than 0.004
O₂ at high rate
More infoHide infoIn full load mode.
4.5% ± 1.8
O₂ at low rate
Not given in MI
Working inlet pressure
More infoHide infoMeasured at the gas valve measuring nipple with check programme P.01 set to 100. Technical data gives G20 gas supply pressure 20.0 mbar.
Gas valve test point
17.0–25.0 mbar
Gas rate at maximum
More infoHide infoHeating mode, G20. The technical data also lists gas flow at P max. in hot water mode: 12: 1.6, 15: 1.9, 18: 2.7, 25: 3.2, 30: 3.8 m³/h.
12
1.3 m³/h
15
1.6 m³/h
18
1.9 m³/h
25
2.7 m³/h
30
3.2 m³/h
Flue integrity
More infoHide infoAt the air inlet test point, boiler at maximum rate (combustion chart, Appendix J).
O₂ ≥ 20.6%
CO₂ < 0.2%

From 0020224338_00 (08.10.2015)

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
Home Regular 12 -A (H-GB)41-044-88NG
Home Regular 15 -A (H-GB)41-044-89NG
Home Regular 18 -A (H-GB)41-044-90NG
Home Regular 25 -A (H-GB)41-044-92NG
Home Regular 30 -A (H-GB)41-044-93NG

Source: Vaillant HOME REGULAR installation and maintenance instructions, 0020224338_00 (08.10.2015).

Sections: 2.3 Applicability of the instructions; 7.7 Checking the gas connection pressure; 7.8 Checking the CO2 content; 7.9 Setting the CO2 content; 7.10 Checking the leak-tightness of the flue gas system; J Combustion chart; K Technical data.

Spotted something wrong? Tell us.

Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.