Worcester Bosch R29 & R40 HE conventional (ZB 7-28 R29 HE, ZB 11-40 R40 HE)

Conventional (heat only) boiler, natural gas, or LPG with a conversion kit

Combustion figures

FigureNatural gas (G20)LPG (G31)
CO₂ at high rate
More infoHide infoFrom Table 14 (MI 7.1), CO₂ reading at max. rated heat output, at the flue gas testing point (234) with the probe about 135 mm in. No tolerance given. Table 14 labels the gases Natural gas type G20 and LPG G31 (propane), with one row for both sizes. The technical data (MI 1.9, Table 2) gives the same figures for both sizes. MI 7 says the setting is factory sealed at maximum and adjusting the rated and min. heat input isn’t necessary.
9.2 %10.8 %
CO₂ at low rate
More infoHide infoThe manual contradicts itself for the R40. Table 14 (MI 7.1), which the gas/air ratio steps use, gives one figure for both sizes: 8.8 % (NG) and 10.5 % (LPG) at min. rated heat output. The technical data (MI 1.9, Table 2) agrees for the R 29 HE but gives 9.2 % (NG) and 10.8 % (LPG) for the R 40 HE, the same as its maximum. The MI doesn’t say which is right. No tolerance given.
R29
8.8 %
R40
8.8 % (Table 14) or 9.2 % (Table 2)
R29
10.5 %
R40
10.5 % (Table 14) or 10.8 % (Table 2)
Maximum CO
Not given in MINot given in MI
CO/CO₂ ratio
Not given in MINot given in MI
O₂
Not given in MINot given in MI
Working inlet pressure
More infoHide infoMI 7 says natural gas appliances must not be operated if the gas supply pressure is below 18 mbar or above 24 mbar, and LPG appliances must not be operated if the supply pressure is below or above 37 mbar (printed like that). MI 5.1 gives the same limits, wording the LPG one as not 37 mbar at the inlet to the appliance. Both say to check at the gas supply pressure test point (7), which Fig. 3 (MI 1.7) shows on the gas valve. The MI doesn’t say whether the boiler should be running. Nominal gas supply pressure (MI 1.9, Table 2): NG G20 20 mbar, LPG 37 mbar. NG G20 appliances are factory set to Wobbe-Index 15 kWh/m³ and 20 mbar supply pressure and sealed (MI 7).
Gas valve test point
18–24 mbar
Gas valve test point
37 mbar
Gas rate at maximum
More infoHide infoMaximum gas flow rate after 10 minutes from lighting (MI 1.9, Table 2), for NG G20 at CVnet 34.02 MJ/m³ and LPG at CVnet 88 MJ/m³ (as printed). Table 2 heads the sizes R 29 HE and R 40 HE, and gives a max. rated heat input of 27.7 kW and 40 kW. Table 18 (MI 9.3) gives a NG gas volume flow rate of 48.5 l/min at display code 100 (27.7 kW heat input), and the MI has no separate table for the R 40 HE.
R29
2.9 m³/h
R40
4.2 m³/h
R29
2.1 kg/h
R40
3.2 kg/h
Flue integrity
More infoHide infoAt the testing point for combustion air (234.1) with the probe about 80 mm in, boiler in chimney sweep mode (MI 7.2.1). The MI words it as O₂ must not be less than 20,6 % and CO₂ must not exceed 0,2 %, and says this checks the gas tightness of a type C13 or C33 flue system.
O₂ ≥ 20.6%
CO₂ ≤ 0.2%
O₂ ≥ 20.6%
CO₂ ≤ 0.2%

From 6 720 611 445 GB (05.04)

Enter service mode for high and low rate

High rate

  1. Hold the service button (spanner) until the display shows – – and the button lights.
  2. Turn the temperature control (radiator symbol, left knob) until the display shows 2.0. After a moment it shows 0.
  3. Turn the function control (right knob) until the display shows 2. for maximum. The display and service button flash.
  4. Or: hold the chimney sweep button until – – shows. Runs at maximum, or at the set heating output if it’s been limited.

Low rate

  1. Turn the function control anti-clockwise until the display shows 1. for minimum.
  2. Turn it back to 2. for maximum.
Ending the test
  • Turn the function control anti-clockwise to the stop (0.), hold the service button until [ ] shows, then set both knobs back.
  • Chimney sweep: hold the chimney sweep button until – – shows. It also ends by itself after 15 minutes.

Models and GC numbers

ModelGC numberGas
ZB 7-28 R29 HE41-311-60NG
ZB 11-40 R40 HE41-311-61NG

Source: Worcester R29 & R40 HE conventional wall mounted condensing boiler for central heating installation and servicing instructions, 6 720 611 445 GB (05.04).

Sections: Cover (GC numbers); 1.7 Function; 1.9 Technical data; 5.1 Commissioning; 7 Converting the appliance to different gas types (checking the gas supply pressure, Table 13 conversion kits); 7.1 Setting the gas/air ratio; 7.2.1 Testing the O₂ or CO₂ level in the combustion air; 7.2.2 Testing CO and CO₂; 9.3 Heating/hot water output settings (N.G).